from various measuring locations (this is the case for the high-voltage side
S1
of the transformer, which is fed
by
M1
and
M2
), no sides are defined for the additional protected object. Nevertheless, other protection func-
tions (not the differential protection) can act on it, such as the overcurrent protection (3-phase on
M5
), the
earth overcurrent protection (1-phase on
X4
), or the restricted earth fault protection, which compares the
triple zero sequence current from
M5
with the earth fault current of
X4
.
[topologie-dreiwicklungstransformators-270503-st, 1, en_GB]
Figure 2-3
Topology of a three-winding transformer as main protected object and a neutral reactor
arranged outside of the protected zone as a further protected object; right hand three-phase
illustration of the neutral reactor
Sides:
S1
High voltage side of the main protected object (power transformer)
S2
Low voltage side of the main protected object (power transformer)
S3
Tertiary winding side of the main protected object (power transformer)
Measuring locations 3-phase, assigned:
M1
Measuring location, assigned to the main protected object, side 1
M2
Measuring location, assigned to the main protected object, side 1
M3
Measuring location, assigned to the main protected object, side 2
M4
Measuring location, assigned to the main protected object, side 3
Measuring locations 3-phase, non-assigned::
M5
Measuring location, not assigned to the main protected object, associated with the neutral reactor
Auxiliary measuring locations, 1-phase:
X4
Measuring location, not assigned to the main protected object, associated with the neutral reactor
Determining the Topology
You have to determine the topology of the main protected object and further objects (if applicable). The
following clarifications are based on the examples given above and the terminology defined above. Further
examples will be given where needed. The necessary and possible settings depend on the type of main
protected object as defined during configuration of the scope of functions (Section
)
festgelegt wurde.
The measuring locations for a single-phase power transformer are treated like 3-phase measuring locations:
From the point of view of measured value conditioning, the single-phase transformer is handled as a threep-
hase transformer with missing phase (L2).
i
i
NOTE
If you have changed the protected object, you will have to check and re-adjust all topological data.
Functions
2.1 General
SIPROTEC 4, 7UT6x, Manual
43
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...