Operating Times of the Definite Time Stages
7UT612
Pickup time / dropout time
for frequency
50 Hz
60 Hz
Minimum pick-up time
Pick-up time, typical
50 ms
55 ms
45 ms
50 ms
Dropout time, approx.
30 ms
30 ms
7UT613/63x
Pickup time / dropout time
Pickup time at frequency
50 Hz
60 Hz
16.7 Hz
Pickup time,- 2 x Pickup Value
1
)
Pickup time,- 10 x Pickup Value
1
)
45 ms
40 ms
39 ms
39 ms
113 ms
88 ms
Dropout time, approx.
25 ms
21 ms
51 ms
1
) for high-speed relays, the pick-up times decrease by 4.5 ms
Dropout to Pickup Ratios
Current stages
approx. 0.95 for
Ι
2
/
Ι
N
≥ 0.5
Frequency
Frequency influence
within the frequency tagging range
Dropout times of the thermal curve
[ausloesezeiten-thermische-kennlinie-schieflast-020830-ho, 1, en_GB]
Figure 4-13
Trip times of the Thermal Characteristic for Unbalanced Load Protection
Technical Data
4.8 Unbalanced Load Protection
SIPROTEC 4, 7UT6x, Manual
433
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...