Undervoltage Protection
Setting Ranges / Increments
Measured quantity
Positive Sequence phase-to-earth voltages as
phase-tophase values
Pickup Thresholds U<, U<<
10.0 V to 125.0 V
Increments 0.1 V
Dropout Ratios DR
(only stages U<, U<<)
1.01 to 1.20
Increments 0.01
Time Delays T U<, T U<<
0.00 s to 60.0 s
or ∞ (unwirksam)
Increments 0.01 s
The set times are pure delay times with definite time protection.
Times
Pickup times
50/60 Hz
approx. 30 ms
16.7 Hz
approx. 70 ms
Dropout times
50/60 Hz
approx. 30 ms
16.7 Hz
approx. 70 ms
Tolerances
Pickup voltages U<, U<<
1 % of setting value or 0.5 V
Delay times T
1 % of setting value or 10 ms
Influencing Variables for Pickup Values
Power supply direct voltage in range
0.8 ≤ U
H
/U
HN
≤ 1.15
≤ 1 %
Temperature in range
–5 °C ≤ Θ
amb
≤ 55 °C
≤ 0.5 %/10 K
Frequency in range 0.95 ≤ f/f
N
≤ 1.05
≤ 1 %
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
≤ 1 %
≤ 1 %
4.14
Technical Data
4.14 Undervoltage Protection
SIPROTEC 4, 7UT6x, Manual
449
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...