[diff-stromdefinition-020926-rei, 1, en_GB]
Figure 2-20
Definition of current direction
•
Through-flowing current under undisturbed conditions or external fault:
Ι
1
flows into the protected zone,
Ι
2
leaves the protected zone, i.e. is negative according tot he definition
of signs, therefore
Ι
2
= –
Ι
1
;
moreover |
Ι
2
| = |
Ι
1
|
Ι
diff
= |
Ι
1
+
Ι
2
| = |
Ι
1
–
Ι
1
| = 0
Ι
stab
= |
Ι
1
| + |
Ι
2
| = |
Ι
1
| + |
Ι
1
| = 2 · |
Ι
1
|
No tripping effect (
Ι
diff
= 0); the stabilisation (
Ι
stab
) corresponds to double the through-flowing current.
•
Internal short-circuit, e.g. fed with equal currents each side:
The following applies
Ι
2
=
Ι
1
; außerdem ist |
Ι
2
| = |
Ι
1
|
Ι
diff
= |
Ι
1
+
Ι
2
| = |
Ι
1
+
Ι
1
| = 2 · |
Ι
1
|
Ι
stab
= |
Ι
1
| + |
Ι
2
| = |
Ι
1
| + |
Ι
1
| = 2 · |
Ι
1
|
Tripping effect (
Ι
diff
) and restraint value (
Ι
stab
) are equal and correspond to the total fault.
•
Internal short-circuit, fed from one side only:
The following applies
Ι
2
= 0
Ι
diff
= |
Ι
1
+
Ι
2
| = |
Ι
1
+ 0| = |
Ι
1
|
Ι
stab
= |
Ι
1
| + |
Ι
2
| = |
Ι
1
| + 0 = |
Ι
1
|
Tripping quantity (
Ι
diff
) and restraint value (
Ι
stab
) are equal and correspond to the single-sided fault
current.
This result shows that for internal fault
Ι
diff
=
Ι
stab
. Thus, the characteristic of internal faults is a straight line
with the slope 1 (45°) in the operation diagram (dash-dotted fault characteristic in
Functions
2.2 Differential Protection
94
SIPROTEC 4, 7UT6x, Manual
C53000-G1176-C230-5, Edition 09.2016
Summary of Contents for SIPROTEC 4 7UT6 Series
Page 394: ...394 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 482: ...482 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 504: ...504 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 522: ...522 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 528: ...528 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 538: ...538 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 664: ...664 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 666: ...666 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...
Page 684: ...684 SIPROTEC 4 7UT6x Manual C53000 G1176 C230 5 Edition 09 2016 ...