Function Control
The function logic coordinates the sequence of both the protective and ancillary functions, processes the func-
tional decisions, and data received from the system.
Pickup Logic for the Entire Device
This section describes the general pickup and spontaneous messages in the device display.
Functional Description
General Device Pickup
The pickup signals for all protection functions in the device are logically OR-combined, and lead to the general
device pickup. It is initiated by the first incoming pickup, ends when the last function drops out and is indi-
cated as general device pickup
Relay PICKUP
.
The general pickup is a prerequisite for a number of internal and external consequential functions. These func-
tions, which are controlled by the general pickup, include:
•
Start of Trip Log: From start of the general device pickup to device drop out, all fault indications are
entered in the trip log.
•
Initialization of fault recording: The storage and maintenance of fault values can also be made dependent
on the occurrence of a trip command.
•
Generation of Spontaneous indications in the device display: Certain fault indications are displayed in the
device display as so-called spontaneous indications (see below “Display—Spontaneous Indications”). This
display can also be made dependent on a general device trip.
Display–Spontaneous Messages
Spontaneous indications are fault indications that appear in the display automatically when general device
pickup has occurred. In the case of 7VE61 and 7VE63 they are the following:
“Protection Pickup”:
the protection function that last picked up
“Protection Trip”:
the protection function that last initiated a trip signal
“PU Time”:
the operating time from the general pickup to the
dropout of the device, the time is given in ms
“Trip time”:
the operating time from general pickup to the first
trip command of the device, in ms
Tripping Logic for the Entire Device
This section comprises a description regarding the general trip and termination of the trip command.
Functional Description
General Trip
The tripping signals for all protective functions are connected by “OR” and generate a message
Relay TRIP
.
Die Auslösesignale aller Schutzfunktionen werden mit ODER verknüpft und führen zur Meldung
Relay TRIP
.
This indiciation, like individual trip indications, can be allocated to an LED or an output relay. It can also be
used as a sum event.
Control of the Trip Command
For controlling the trip command the following applies:
2.13
2.13.1
2.13.1.1
2.13.2
2.13.2.1
Functions
2.13 Function Control
118
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...