If a protective function is set to
Block. Relais
, it is blocked for the activation of the output relay. The
other protective functions are not affected by this.
•
A trip command once transmitted is stored (see
). At the same time, the minimum trip
command duration
TMin TRIP CMD
is started. This trip signal duration timer ensures the trip signal is
transmitted to the circuit breaker for a sufficient amount of time, even if the function which issued the
trip signal drops out quickly. The trip signal is only terminated after all protection Functions drop out AND
the minimum trip signal duration expires.
•
Finally, it is possible to latch the trip signal until it is manually reset (lockout function). This allows inter-
locking the circuit breaker against reclosing until the cause of the malfunction has been clarified and the
interlock has been manually reset. The reset takes place either by pressing the LED reset key or by acti-
vating an appropriately masked binary input (>Reset LED). A precondition, of course, is that the circuit
breaker trip coil – as usual – remains blocked as long as the trip signal is present, and the trip coil current
is interrupted by the auxiliary contact of the circuit breaker.
[absteuerung-des-ausloesekommando-020828-ho, 1, en_GB]
Figure 2-51
Terminating the Trip Signal, Example of a Protective Function
Setting Notes
Command Duration
The minimum trip command duration 280
TMin TRIP CMD
was described already in Section
. It is valid for all protection functions which can issue a trip command.
2.13.2.2
Functions
2.13 Function Control
SIPROTEC 4, 7VE61 and 7VE63, Manual
119
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...