column of the dialog box you can switch each item to the opposite state after entering password no. 6 (for
hardware test menus). Thus, you can energize every single output relay to check the wiring between
protected device and the system without having to create the alarm allocated to it.
The procedure is described in detail in Chapter Mounting and Commissioning.
Creating a Test Fault Record
During commissioning energization sequences should be carried out, to check the stability of the protection
also during closing operations. Oscillographic event recordings contain the maximum information about the
behaviour of the protection.
Along with the capability of storing fault recordings via pickup of the protection function, the 7VE61 and
7VE63 also has the capability of initiating a measured value recording using the operator control program
DIGSI, via the serial interface and via binary inputs. For the latter, event
>Trig.Wave.Cap.
must be allo-
cated to a binary input. Triggering of the recording then occurs, for example, via the binary input when the
protection object is energized.
An oscillographic recording that is externally triggered (that is, without a protective element pickup or device
trip) is processed by the device as a normal oscillographic recording, and has a number for establishing a
sequence. However, these recordings are not displayed in the fault log buffer in the display, as they are not
network fault events.
The procedure is described in detail in Chapter Mounting and Commissioning.
Functions
2.14 Auxiliary Functions
130
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...