Binary Inputs
Binary Inputs
19 V Threshold
1)
88 V Threshold
3)
176 V Threshold
3)
BI11
X29/X30
L
M
H
BI12
X31/X32
L
M
H
BI13
X33/X34
L
M
H
BI14
X35/X36
L
M
H
1)
Factory settings for devices with rated power supply voltages of DC 24 V to 125 V
2)
Factory settings for devices with rated power supply voltages of DC 110 to 220 V and AC 115 V to 230 V
3)
Use only with control voltages 220 V or 250 V
Contact Mode
With models 7VE63 binary output BO12 can be changed from normally open to normally closed operation.
The following table shows the setting of jumper X40 regarding the contact mode.
Table 3-9
Jumper settings for Contact mode of the binary output BO12 on the C–I/O-1 board
Jumper
Open in quiescent state
Closed in quiescent state
Presetting
X40
1–2
2–3
1–2
Bus address
Jumpers X71, X72 and X73 on the Input/Output C-I/O-1 board are used to set the bus address and may not be
changed. The following Table shows the factory setting of the jumpers.
Table 3-10
Jumper settings for Bus address on the C–I/O–1 board for 7VE63
Jumper
Presetting
X71
H
X72
L
X73
H
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC 4, 7VE61 and 7VE63, Manual
153
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...