Figure 3-22
Testing the measuring voltages in the measuring field — Example 2
If there is no transformer between the two measuring points – as shown in the above examples – address
6122
ANGLE ADJUSTM.
must be set to
0
°.
If the measurement is made across a transformer, this angle setting must correspond to the phase rotation
through which the vector group of the transformer (as seen from the feeder in the direction of the busbar)
rotates the voltage. There is an example in the setting notes of the synchronization function.
Checking with the Power Transformer
In the synchronization range, it is included a power transformer with tap changers is included as shown in
. There are different methods to perform a test. The method without having the generator in oper-
ation is described. The generator circuit breaker including the isolator is continuously open and it is secured
against switching.
Mounting and Commissioning
3.3 Commissioning
180
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...