Set the fault record in the functional scope to instantaneous values record and trigger with parameter
401
WAVEFORMTRIGGER
to
Save w. TRIP
.
•
Select the synchronization functional group and start the synchronism. The paralleling device is immedi-
ately started.
•
Read the fault record out and measure the closing time with SIGRA (see
). Use both cursors
and the time measurement function for that purpose. The occurrence of the 2nd voltage signals the
closed poles.
•
Set the calculated time under address 6120 as
T-CB close
. Round off to the next lower settable value.
Proceed for all used synchronizing functions 2 to 8 in the same way.
•
Set again the parameter 6x07 or 6x08 to the original value.
[ve6-ibs-ls-eigenzeitmessung, 1, en_GB]
Figure 3-25
Web Tool — Measurement of the circuit breaker closing time
Test Operation with the Synchronization Function
Prerequisites
The setting values are checked again (see Section “Setting Notes” of the Synchronization Function in Chapter
2).
The circuit breaker is disconnected. The close command for the circuit breaker as well as some setpoint
commands are interrupted (disconnect the close and setpoint command). The system voltage is switched
through the measurement.
3.3.10
Mounting and Commissioning
3.3 Commissioning
SIPROTEC 4, 7VE61 and 7VE63, Manual
183
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...