Paralleling Functions
Operating Modes
Synchrocheck
Synchronism check
dead-line / live-bus
dead-bus / live-line
dead bus and dead line
bypassing
or combination of the above
Switching Synchronous Systems
Switching at frequence equal
Switching Asynchronous Systems
Closing the circuit breaker under asynchronous power
conditions taking into consideration the circuit breaker
operating time
Voltages
Maximum operating voltage U
max
20 V to 140 V
Increments 1 V
Minimum operating voltage U
min
20 V to 125 V
Increments 1 V
U1, U2 (U<, for de-energization)
1 V to 60 V
Increments 1 V
U1, U2 (U>, for live-line)
20 V to 140 V
Increments 1 V
Tolerances
1 % of pickup value or 0.5 V
Drop-off to pick-up ratio
approx. 0.9 (U>) bzw. 1.1 (U<)
ΔU-Measurement
Voltage difference ΔU
0.0 V to 40.0 V
Increments 0.1 V
Tolerances
max. 0.5 V; typical 0.2 V
Drop-off to pick-up ratio
approx. 1.05
Matching
Angle Correction of the Vector group
0° to 359°
Increments 1°
Matching of the voltage transformers U1/U2
0.50 to 2.00
Increments 0.01
Synchronous Power Conditions
Δα-measurement
2° to 80°
Increments 1°
Tolerances
0.5° at nominal frequency and small frequency difference
Dropout difference of the phase values
1°
Δf-measurement
0.00 Hz to 2.00 Hz
Increments 0.01 Hz
Tolerances
10 mHz
Dropout Value Frequency
20 mHz
Release delay
0.00 s to 60.00 s
Increments 0.01 s
Asynchronous Power Conditions
Δf-measurement
0.00 Hz to 2.00 Hz
Increments 0.01 Hz
Tolerances
10 mHz
4.2
Technical Data
4.2 Paralleling Functions
SIPROTEC 4, 7VE61 and 7VE63, Manual
203
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...