Overvoltage Protection
Setting Ranges/Increments
Measured Quantity
Fundamental component of one of the undervoltage
voltages connected to the measuring inputs (selectable)
Pickup thresholds U>, U>>
30.0 V to 200.0 V
Increments 0.1 V
Dropout ratio U>, U>>
0.90 to 0.99
Increments 0.01
Time Delays T U>, T U>>
0.00 s to 60.00 s
or ∞ (ineffective)
Increments 0.01 s
The set times are pure delay times.
Operating Times
Pickup times/dropout times
approx. 55 ms at f
N
= 50 Hz
approx. 48 ms at f
N
= 60 Hz
approx. 145 ms at f
N
= 16.7 Hz
Tolerances
Pickup voltages U<, U<<
1 % of setting value or 0.5 V
Delay times T
1 % of setting value or 10 ms
Influencing Variables for Pickup Values
Power supply direct voltage in range 0.8 ≤ U
Aux
/U
AuxN
≤ 1.15
≤ 1 %
Temperature in range –5 °C ≤ Θ
amb
≤ 55 °C
≤ 0.5 %/10 K
Frequency in range 0.95 ≤ f/f
N
≤ 1.05
≤ 1 %
Harmonics
- up to 10 % 3rd harmonic
- up to 10 % 5th harmonic
≤ 1 %
≤ 1 %
4.5
Technical Data
4.5 Overvoltage Protection
SIPROTEC 4, 7VE61 and 7VE63, Manual
207
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...