Addr.
Parameter
Function
Setting Options
Default Setting
Comments
4502
df1/dt >/<
df/dt Protect.
-df/dt<
+df/dt>
-df/dt<
Mode of Threshold (df1/dt
>/<)
4503
STAGE df1/dt
df/dt Protect.
0.1 .. 10.0 Hz/s
1.0 Hz/s
Pickup Value of df1/dt Stage
4504
STAGE df1/dt
df/dt Protect.
0.1 .. 3.0 Hz/s
0.3 Hz/s
Pickup Value of df1/dt Stage
4505
T df1/dt
df/dt Protect.
0.00 .. 60.00 sec
0.50 sec
Time Delay of df1/dt Stage
4506
df1/dt & f1
df/dt Protect.
OFF
ON
OFF
AND logic with pickup of
stage f1
4507
df2/dt >/<
df/dt Protect.
-df/dt<
+df/dt>
-df/dt<
Mode of Threshold (df2/dt
>/<)
4508
STAGE df2/dt
df/dt Protect.
0.1 .. 10.0 Hz/s
1.0 Hz/s
Pickup Value of df2/dt Stage
4509
STAGE df2/dt
df/dt Protect.
0.1 .. 3.0 Hz/s
0.3 Hz/s
Pickup Value of df2/dt Stage
4510
T df2/dt
df/dt Protect.
0.00 .. 60.00 sec
0.50 sec
Time Delay of df2/dt Stage
4511
df2/dt & f2
df/dt Protect.
OFF
ON
OFF
AND logic with pickup of
stage f2
4512
df3/dt >/<
df/dt Protect.
-df/dt<
+df/dt>
-df/dt<
Mode of Threshold (df3/dt
>/<)
4513
STAGE df3/dt
df/dt Protect.
0.1 .. 10.0 Hz/s
4.0 Hz/s
Pickup Value of df3/dt Stage
4514
STAGE df3/dt
df/dt Protect.
0.1 .. 3.0 Hz/s
1.3 Hz/s
Pickup Value of df3/dt Stage
4515
T df3/dt
df/dt Protect.
0.00 .. 60.00 sec
0.00 sec
Time Delay of df3/dt Stage
4516
df3/dt & f3
df/dt Protect.
OFF
ON
OFF
AND logic with pickup of
stage f3
4517
df4/dt >/<
df/dt Protect.
-df/dt<
+df/dt>
-df/dt<
Mode of Threshold (df4/dt
>/<)
4518
STAGE df4/dt
df/dt Protect.
0.1 .. 10.0 Hz/s
4.0 Hz/s
Pickup Value of df4/dt Stage
4519
STAGE df4/dt
df/dt Protect.
0.1 .. 3.0 Hz/s
1.3 Hz/s
Pickup Value of df4/dt Stage
4520
T df4/dt
df/dt Protect.
0.00 .. 60.00 sec
0.00 sec
Time Delay of df4/dt Stage
4521
df4/dt & f4
df/dt Protect.
OFF
ON
OFF
AND logic with pickup of
stage f4
4522
U MIN
df/dt Protect.
10.0 .. 125.0 V
65.0 V
Minimum Operating
Voltage Umin
4523A df1/2 HYSTERES.
df/dt Protect.
0.02 .. 0.99 Hz/s
0.10 Hz/s
Reset Hysteresis for df1/dt &
df2/dt
4524A df1/2 M-WINDOW
df/dt Protect.
1 .. 25 Cycle
5 Cycle
Measuring Window for
df1/dt & df2/dt
4525A df3/4 HYSTERES.
df/dt Protect.
0.02 .. 0.99 Hz/s
0.40 Hz/s
Reset Hysteresis for df3/dt &
df4/dt
4526A df3/4 M-WINDOW
df/dt Protect.
1 .. 25 Cycle
5 Cycle
Measuring Window for
df3/dt & df4/dt
4527
MEAS. INPUT
df/dt Protect.
Ua
Ub
Uc
Ud
Ue
Uf
Ua
Used Measuring Input
4601
VECTOR JUMP
Vector Jump
OFF
ON
Block relay
OFF
Jump of Voltage Vector
4602
DELTA PHI
Vector Jump
2 .. 30 °
10 °
Jump of Phasor DELTA PHI
Functions, Settings, Information
E.2 Settings
262
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...