Addr.
Parameter
Function
Setting Options
Default Setting
Comments
6174
T U PAUSE
SYNC function 1 0.00 .. 32.00 sec
5.00 sec
Transient time of the U-
controller
6175A SMOOTHING U
SYNC function 1 1 .. 100
1
Smoothing factor for the
voltage
6176A (U/Un) / (f/fn)
SYNC function 1 1.00 .. 1.40
1.10
Maximum permissible over-
excitation
6180
f BALANCING
SYNC function 1 OFF
Pulse
OFF
Frequency balancing
6181
T f PULS MIN
SYNC function 1 10 .. 1000 ms
20 ms
Minimum pulse duration for
f balancing
6182
T f PULS MAX
SYNC function 1 1.00 .. 32.00 sec
1.00 sec
Maximum pulse duration
for f balancing
6183
df2 / dt
SYNC function 1 0.05 .. 5.00 Hz/s
1.00 Hz/s
df/dt of the controller
6184
T f PAUSE
SYNC function 1 0.00 .. 32.00 sec
5.00 sec
Transient time of the f-
controller
6185
Δf SET POINT
SYNC function 1 -1.00 .. 1.00 Hz
0.04 Hz
Set point for frequency
balancing
6186A SMOOTHING f
SYNC function 1 1 .. 100
1
Smoothing factor for the
frequency
6187
KICK PULSE
SYNC function 1 OFF
ON
ON
Release of kick pulses
6188A Δf KICK
SYNC function 1 -0.10 .. 0.10 Hz
0.04 Hz
df for the kick pulse
6189A T SW-ON MIN
SYNC function 1 0.2 .. 1000.0 sec
5.0 sec
Min time to switch-on
without balancing
6201
Synchronizing
SYNC function 2 ON
OFF
OFF
Synchronizing Function
6202
SyncSD
SYNC function 2 OBJVERWparaMEIN-
STELL
none
synchronizable switching
device
6203
Umin
SYNC function 2 20 .. 125 V
90 V
Minimum voltage limit:
Umin
6204
Umax
SYNC function 2 20 .. 140 V
110 V
Maximum voltage limit:
Umax
6205
U<
SYNC function 2 1 .. 60 V
5 V
Threshold U1, U2 without
voltage
6206
U>
SYNC function 2 20 .. 140 V
80 V
Threshold U1, U2 with
voltage
6207
SYNC U1<U2>
SYNC function 2 YES
NO
NO
ON-Command at U1< and
U2>
6208
SYNC U1>U2<
SYNC function 2 YES
NO
NO
ON-Command at U1> and
U2<
6209
SYNC U1<U2<
SYNC function 2 YES
NO
NO
ON-Command at U1< and
U2<
6211A TSUP VOLTAGE
SYNC function 2 0.0 .. 60.0 sec
0.1 sec
Supervision time Dead
Line / Dead Bus
6212
T-SYN. DURATION
SYNC function 2 0.01 .. 1200.00 sec
1200.00 sec
Maximum duration of
synchronism-check
6213
PHASE SEQUENCE
SYNC function 2 NO
L1 L2 L3
L1 L3 L2
NO
Phase sequence check
Functions, Settings, Information
E.2 Settings
SIPROTEC 4, 7VE61 and 7VE63, Manual
265
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...