Addr.
Parameter
Function
Setting Options
Default Setting
Comments
6404
Umax
SYNC function 4 20 .. 140 V
110 V
Maximum voltage limit:
Umax
6405
U<
SYNC function 4 1 .. 60 V
5 V
Threshold U1, U2 without
voltage
6406
U>
SYNC function 4 20 .. 140 V
80 V
Threshold U1, U2 with
voltage
6407
SYNC U1<U2>
SYNC function 4 YES
NO
NO
ON-Command at U1< and
U2>
6408
SYNC U1>U2<
SYNC function 4 YES
NO
NO
ON-Command at U1> and
U2<
6409
SYNC U1<U2<
SYNC function 4 YES
NO
NO
ON-Command at U1< and
U2<
6411A TSUP VOLTAGE
SYNC function 4 0.0 .. 60.0 sec
0.1 sec
Supervision time Dead
Line / Dead Bus
6412
T-SYN. DURATION
SYNC function 4 0.01 .. 1200.00 sec
1200.00 sec
Maximum duration of
synchronism-check
6413
PHASE SEQUENCE
SYNC function 4 NO
L1 L2 L3
L1 L3 L2
NO
Phase sequence check
6420
T-CB close
SYNC function 4 10 .. 1000 ms
2147483647 ms
Closing (operating) time of
CB
6421
Balancing U1/U2
SYNC function 4 0.50 .. 2.00
1.00
Balancing factor U1/U2
6422A ANGLE ADJUSTM.
SYNC function 4 0 .. 359 °
0 °
Angle adjustment (trans-
former)
6424
VT Un1, primary
SYNC function 4 0.10 .. 999.99 kV
15.75 kV
VT nominal voltage U1,
primary
6425
VT Un2, primary
SYNC function 4 0.10 .. 999.99 kV
15.75 kV
VT nominal voltage U2,
primary
6426
Unom SECONDARY SYNC function 4 80 .. 125 V
100 V
Rated Secondary Voltage
(Ph-Ph)
6427
T CLS CMD MIN
SYNC function 4 0.01 .. 10.00 sec
0.10 sec
Min close command time of
the CB
6430
dU ASYN U2>U1
SYNC function 4 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6431
dU ASYN U2<U1
SYNC function 4 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6432
df ASYN f2>f1
SYNC function 4 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2>f1
6433
df ASYN f2<f1
SYNC function 4 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2<f1
6440
SYNC PERMIS.
SYNC function 4 NO
YES
NO
Switching at synchronous
conditions
6441
F SYNCHRON
SYNC function 4 0.01 .. 0.04 Hz
0.01 Hz
Frequency threshold ASYN
<--> SYN
6442
dU SYN U2>U1
SYNC function 4 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6443
dU SYN U2<U1
SYNC function 4 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6444
dα SYN α2>α1
SYNC function 4 2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
Functions, Settings, Information
E.2 Settings
270
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...