Addr.
Parameter
Function
Setting Options
Default Setting
Comments
6445
dα SYN α2<α1
SYNC function 4 2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
6446
T SYNC-DELAY
SYNC function 4 0.00 .. 60.00 sec
10.00 sec
Release delay at synchro-
nous conditions
6450
dU SYNC U2>U1
SYNC function 4 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6451
dU SYNC U2<U1
SYNC function 4 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6452
df SYNC f2>f1
SYNC function 4 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2>f1
6453
df SYNC f2<f1
SYNC function 4 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2<f1
6454
dα SYNC α2> α1
SYNC function 4 2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
6455
dα SYNC α2< α1
SYNC function 4 2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
6460
TAP CHG. OBJ.
SYNC function 4 OBJVERWparaMEIN-
STELL
none
Tap changer object
6461
#STEP NOM. VOLT
SYNC function 4 -62 .. 62
0
# of tap changer at nom.
voltage
6462
TAP STEP
SYNC function 4 -20.00 .. 20.00 %
0.00 %
Step size tap changer
6470
U BALANCING
SYNC function 4 OFF
Tap changer
Pulse
OFF
Voltage balancing
6471
T U PULS MIN
SYNC function 4 10 .. 1000 ms
100 ms
Minimum pulse duration for
U balancing
6472
T U PULS MAX
SYNC function 4 1.00 .. 32.00 sec
1.00 sec
Maximum pulse duration
for U balancing
6473
dU2 / dt
SYNC function 4 0.1 .. 50.0 V/s
2.0 V/s
dU/dt of the controller
6474
T U PAUSE
SYNC function 4 0.00 .. 32.00 sec
5.00 sec
Transient time of the U-
controller
6475A SMOOTHING U
SYNC function 4 1 .. 100
1
Smoothing factor for the
voltage
6476A (U/Un) / (f/fn)
SYNC function 4 1.00 .. 1.40
1.10
Maximum permissible over-
excitation
6480
f BALANCING
SYNC function 4 OFF
Pulse
OFF
Frequency balancing
6481
T f PULS MIN
SYNC function 4 10 .. 1000 ms
20 ms
Minimum pulse duration for
f balancing
6482
T f PULS MAX
SYNC function 4 1.00 .. 32.00 sec
1.00 sec
Maximum pulse duration
for f balancing
6483
df2 / dt
SYNC function 4 0.05 .. 5.00 Hz/s
1.00 Hz/s
df/dt of the controller
6484
T f PAUSE
SYNC function 4 0.00 .. 32.00 sec
5.00 sec
Transient time of the f-
controller
6485
Δf SET POINT
SYNC function 4 -1.00 .. 1.00 Hz
0.04 Hz
Set point for frequency
balancing
6486A SMOOTHING f
SYNC function 4 1 .. 100
1
Smoothing factor for the
frequency
6487
KICK PULSE
SYNC function 4 OFF
ON
ON
Release of kick pulses
6488A Δf KICK
SYNC function 4 -0.10 .. 0.10 Hz
0.04 Hz
df for the kick pulse
Functions, Settings, Information
E.2 Settings
SIPROTEC 4, 7VE61 and 7VE63, Manual
271
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...