Addr.
Parameter
Function
Setting Options
Default Setting
Comments
6541
F SYNCHRON
SYNC function 5 0.01 .. 0.04 Hz
0.01 Hz
Frequency threshold ASYN
<--> SYN
6542
dU SYN U2>U1
SYNC function 5 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6543
dU SYN U2<U1
SYNC function 5 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6544
dα SYN α2>α1
SYNC function 5 2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
6545
dα SYN α2<α1
SYNC function 5 2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
6546
T SYNC-DELAY
SYNC function 5 0.00 .. 60.00 sec
10.00 sec
Release delay at synchro-
nous conditions
6550
dU SYNC U2>U1
SYNC function 5 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2>U1
6551
dU SYNC U2<U1
SYNC function 5 0.0 .. 40.0 V
2.0 V
Maximum voltage differ-
ence U2<U1
6552
df SYNC f2>f1
SYNC function 5 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2>f1
6553
df SYNC f2<f1
SYNC function 5 0.00 .. 2.00 Hz
0.10 Hz
Maximum frequency differ-
ence f2<f1
6554
dα SYNC α2> α1
SYNC function 5 2 .. 80 °
10 °
Maximum angle difference
alpha2>alpha1
6555
dα SYNC α2< α1
SYNC function 5 2 .. 80 °
10 °
Maximum angle difference
alpha2<alpha1
6560
TAP CHG. OBJ.
SYNC function 5 OBJVERWparaMEIN-
STELL
none
Tap changer object
6561
#STEP NOM. VOLT
SYNC function 5 -62 .. 62
0
# of tap changer at nom.
voltage
6562
TAP STEP
SYNC function 5 -20.00 .. 20.00 %
0.00 %
Step size tap changer
6570
U BALANCING
SYNC function 5 OFF
Tap changer
Pulse
OFF
Voltage balancing
6571
T U PULS MIN
SYNC function 5 10 .. 1000 ms
100 ms
Minimum pulse duration for
U balancing
6572
T U PULS MAX
SYNC function 5 1.00 .. 32.00 sec
1.00 sec
Maximum pulse duration
for U balancing
6573
dU2 / dt
SYNC function 5 0.1 .. 50.0 V/s
2.0 V/s
dU/dt of the controller
6574
T U PAUSE
SYNC function 5 0.00 .. 32.00 sec
5.00 sec
Transient time of the U-
controller
6575A SMOOTHING U
SYNC function 5 1 .. 100
1
Smoothing factor for the
voltage
6576A (U/Un) / (f/fn)
SYNC function 5 1.00 .. 1.40
1.10
Maximum permissible over-
excitation
6580
f BALANCING
SYNC function 5 OFF
Pulse
OFF
Frequency balancing
6581
T f PULS MIN
SYNC function 5 10 .. 1000 ms
20 ms
Minimum pulse duration for
f balancing
6582
T f PULS MAX
SYNC function 5 1.00 .. 32.00 sec
1.00 sec
Maximum pulse duration
for f balancing
6583
df2 / dt
SYNC function 5 0.05 .. 5.00 Hz/s
1.00 Hz/s
df/dt of the controller
Functions, Settings, Information
E.2 Settings
SIPROTEC 4, 7VE61 and 7VE63, Manual
273
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...