Addr.
Parameter
Function
Setting Options
Default Setting
Comments
6584
T f PAUSE
SYNC function 5 0.00 .. 32.00 sec
5.00 sec
Transient time of the f-
controller
6585
Δf SET POINT
SYNC function 5 -1.00 .. 1.00 Hz
0.04 Hz
Set point for frequency
balancing
6586A SMOOTHING f
SYNC function 5 1 .. 100
1
Smoothing factor for the
frequency
6587
KICK PULSE
SYNC function 5 OFF
ON
ON
Release of kick pulses
6588A Δf KICK
SYNC function 5 -0.10 .. 0.10 Hz
0.04 Hz
df for the kick pulse
6589A T SW-ON MIN
SYNC function 5 0.2 .. 1000.0 sec
5.0 sec
Min time to switch-on
without balancing
6601
Synchronizing
SYNC function 6 ON
OFF
OFF
Synchronizing Function
6602
SyncSD
SYNC function 6 OBJVERWparaMEIN-
STELL
none
synchronizable switching
device
6603
Umin
SYNC function 6 20 .. 125 V
90 V
Minimum voltage limit:
Umin
6604
Umax
SYNC function 6 20 .. 140 V
110 V
Maximum voltage limit:
Umax
6605
U<
SYNC function 6 1 .. 60 V
5 V
Threshold U1, U2 without
voltage
6606
U>
SYNC function 6 20 .. 140 V
80 V
Threshold U1, U2 with
voltage
6607
SYNC U1<U2>
SYNC function 6 YES
NO
NO
ON-Command at U1< and
U2>
6608
SYNC U1>U2<
SYNC function 6 YES
NO
NO
ON-Command at U1> and
U2<
6609
SYNC U1<U2<
SYNC function 6 YES
NO
NO
ON-Command at U1< and
U2<
6611A TSUP VOLTAGE
SYNC function 6 0.0 .. 60.0 sec
0.1 sec
Supervision time Dead
Line / Dead Bus
6612
T-SYN. DURATION
SYNC function 6 0.01 .. 1200.00 sec
1200.00 sec
Maximum duration of
synchronism-check
6613
PHASE SEQUENCE
SYNC function 6 NO
L1 L2 L3
L1 L3 L2
NO
Phase sequence check
6620
T-CB close
SYNC function 6 10 .. 1000 ms
2147483647 ms
Closing (operating) time of
CB
6621
Balancing U1/U2
SYNC function 6 0.50 .. 2.00
1.00
Balancing factor U1/U2
6622A ANGLE ADJUSTM.
SYNC function 6 0 .. 359 °
0 °
Angle adjustment (trans-
former)
6624
VT Un1, primary
SYNC function 6 0.10 .. 999.99 kV
15.75 kV
VT nominal voltage U1,
primary
6625
VT Un2, primary
SYNC function 6 0.10 .. 999.99 kV
15.75 kV
VT nominal voltage U2,
primary
6626
Unom SECONDARY SYNC function 6 80 .. 125 V
100 V
Rated Secondary Voltage
(Ph-Ph)
6627
T CLS CMD MIN
SYNC function 6 0.01 .. 10.00 sec
0.10 sec
Min close command time of
the CB
Functions, Settings, Information
E.2 Settings
274
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...