Addr.
Parameter
Function
Setting Options
Default Setting
Comments
6771
T U PULS MIN
SYNC function 7 10 .. 1000 ms
100 ms
Minimum pulse duration for
U balancing
6772
T U PULS MAX
SYNC function 7 1.00 .. 32.00 sec
1.00 sec
Maximum pulse duration
for U balancing
6773
dU2 / dt
SYNC function 7 0.1 .. 50.0 V/s
2.0 V/s
dU/dt of the controller
6774
T U PAUSE
SYNC function 7 0.00 .. 32.00 sec
5.00 sec
Transient time of the U-
controller
6775A SMOOTHING U
SYNC function 7 1 .. 100
1
Smoothing factor for the
voltage
6776A (U/Un) / (f/fn)
SYNC function 7 1.00 .. 1.40
1.10
Maximum permissible over-
excitation
6780
f BALANCING
SYNC function 7 OFF
Pulse
OFF
Frequency balancing
6781
T f PULS MIN
SYNC function 7 10 .. 1000 ms
20 ms
Minimum pulse duration for
f balancing
6782
T f PULS MAX
SYNC function 7 1.00 .. 32.00 sec
1.00 sec
Maximum pulse duration
for f balancing
6783
df2 / dt
SYNC function 7 0.05 .. 5.00 Hz/s
1.00 Hz/s
df/dt of the controller
6784
T f PAUSE
SYNC function 7 0.00 .. 32.00 sec
5.00 sec
Transient time of the f-
controller
6785
Δf SET POINT
SYNC function 7 -1.00 .. 1.00 Hz
0.04 Hz
Set point for frequency
balancing
6786A SMOOTHING f
SYNC function 7 1 .. 100
1
Smoothing factor for the
frequency
6787
KICK PULSE
SYNC function 7 OFF
ON
ON
Release of kick pulses
6788A Δf KICK
SYNC function 7 -0.10 .. 0.10 Hz
0.04 Hz
df for the kick pulse
6789A T SW-ON MIN
SYNC function 7 0.2 .. 1000.0 sec
5.0 sec
Min time to switch-on
without balancing
6801
Synchronizing
SYNC function 8 ON
OFF
OFF
Synchronizing Function
6802
SyncSD
SYNC function 8 OBJVERWparaMEIN-
STELL
none
synchronizable switching
device
6803
Umin
SYNC function 8 20 .. 125 V
90 V
Minimum voltage limit:
Umin
6804
Umax
SYNC function 8 20 .. 140 V
110 V
Maximum voltage limit:
Umax
6805
U<
SYNC function 8 1 .. 60 V
5 V
Threshold U1, U2 without
voltage
6806
U>
SYNC function 8 20 .. 140 V
80 V
Threshold U1, U2 with
voltage
6807
SYNC U1<U2>
SYNC function 8 YES
NO
NO
ON-Command at U1< and
U2>
6808
SYNC U1>U2<
SYNC function 8 YES
NO
NO
ON-Command at U1> and
U2<
6809
SYNC U1<U2<
SYNC function 8 YES
NO
NO
ON-Command at U1< and
U2<
6811A TSUP VOLTAGE
SYNC function 8 0.0 .. 60.0 sec
0.1 sec
Supervision time Dead
Line / Dead Bus
Functions, Settings, Information
E.2 Settings
278
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...