No.
Information
Type of
Informa-
tion
Comments
25011
dU:
VI
Voltagedifference at switch on
25012
df:
VI
Frequencydifference at switch on
25013
dα:
VI
Angledifference at switch on
25059
>Break. Contact
SP
>Breaker contacts
Change Group
Up to four independent setting groups can be created for establishing protection function settings.
Setting groups enable the user to save the various function settings for different applications and to retrieve
these settings quickly. All setting groups are stored in the device. Only one setting group is active.
During operation the user can locally switch between setting groups, using the operator panel, binary inputs
(if so configured), the service interface per PC, or via the system interface.
A setting group includes the setting values for all functions that have been selected as
Enabled
during
). In 7VE61 and 7VE63 devices, four independent setting
groups (A to D) are available. Whereas setting values may vary, the selected functions of each setting group
remain the same.
Setting Notes
General
If multiple setting groups are not required, group A is the default selection. Then, the rest of this section is not
applicable.
If the changeover option is desired, group changeover must be set to
Grp Chge OPTION
=
Enabled
(address 103) when the function extent is configured. For the setting of the function parameters, each of the
required setting groups A to D (a maximum of 4) must be configured in sequence. The SIPROTEC 4 System
Description gives further information on how to copy setting groups or reset them to their status at delivery
and also how to change from one setting group to another.
Subsection
of this manual tells you how to change between several setting
groups externally via binary inputs.
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
302
CHANGE
Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A
Change to Another Setting Group
Information List
No.
Information
Type of
Informa-
tion
Comments
-
P-GrpA act
IntSP
Setting Group A is active
-
P-GrpB act
IntSP
Setting Group B is active
-
P-GrpC act
IntSP
Setting Group C is active
-
P-GrpD act
IntSP
Setting Group D is active
7
>Set Group Bit0
SP
>Setting Group Select Bit 0
2.1.5
2.1.5.1
2.1.5.2
2.1.5.3
Functions
2.1 General
SIPROTEC 4, 7VE61 and 7VE63, Manual
33
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...