[logik-stellbefehle-spannung-290403-kn, 1, en_GB]
Figure 2-22
Logic diagram for generation of voltage balancing pulses
[logik-stellbefehle-frequenz-040303-oz, 1, en_GB]
Figure 2-23
Logic diagram for generation of frequency balancing pulses
If the synchronous operating range is detected, i.e. the frequency difference Δf is less than parameter 6141
F
SYNCHRON
, the connection conditions however are not yet fulfilled (ΔU and Δα are not in the admissible
range), then “Kick impulses” may be issued if the voltage controllers will not converge within a short time. This
is the case if the time to synchronism exceeds a particular time.
If for the parameter 6132
df ASYN f2>f1
a nonzero value is set, i.e. parallel switching from the oversyn-
chronous range is permitted, then the target value 6188
Δf KICK
should be set to a positive value because
kicking is done in the target value direction
Δf KICK
.
Functions
2.2 Paralleling Functions
58
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...