Parameter 6141
F SYNCHRON
serves as an automatic threshold between synchronous and asynchronous
switching. If the frequency difference is below the specified threshold, the power systems are considered to
be synchronous and the regulations for synchronous switching apply. If it is above the threshold, the
switching is asynchronous with consideration of the time left until the voltages are in phase.
A raising of the threshold may be necessary if drives (e.g. reciprocating compressor) burden the power system
differently in each half cycle and thus negatively influence frequency measurement accuracy.
Parameters 6142
dU SYNC U2>U1
and 6143
dU SYNC U2<U1
allowed the admissible voltage differences to
be set asymmetrically also. The setting value can actually be selected higher than for asynchronous condi-
tions. This is dictated by the system conditions (e.g. greater voltage drops due to current limiting reactor).
Parameters 6144
dα SYNC α2> α1
and 6145
dα SYNC α2< α1
restrict the operating range for synchro-
nous switching with regard to admissible angle difference. These two parameters allow an asymmetrical
switching range to be configured (see also
).
The preset value for the angle must possibly be increased if current limiting reactors cause a larger phase shift.
This however increases the compensation current when switching near the limits.
Moreover, the enable time delay
T SYNC-DELAY
(address 6146) can be set after which all synchronous
conditions must at least be fulfilled for the closing command to be generated. A particular degree of power
system quiescence is then awaited. The default setting of
10 s
has proven to be a good value.
[zuschaltenbeisynchronennetzbedingungen-150502-kn, 1, en_GB]
Figure 2-33
Switching under synchronous system conditions
Ranges in the U,f Diagram
shows the setting parameters both for synchronous as well as asynchronous conditions, in the U, f
diagram. With synchronous power systems the frequency band is in principle very narrow.
Functions
2.2 Paralleling Functions
68
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...