Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
6001
COM. TESTSYNC.
OFF
ON
OFF
Test synchronization (Commis-
sioning)
Information List
No.
Information
Type of
Informa-
tion
Comments
222.0043 >Sync. MeasOnly
SP
>Sync. Measurement Only
222.2011 >Sync Start
SP
>Sync. Start of Synchronization
222.2012 >Sync Stop
SP
>Sync. Stop of Synchronization
222.2013 >Sync U1>U2<
SP
>Sync. Switch to U1> and U2<
222.2014 >Sync U1<U2>
SP
>Sync. Switch to U1< and U2>
222.2015 >Sync U1<U2<
SP
>Sync. Switch to U1< and U2<
222.2027 Sync. U1> U2<
OUT
Sync. Condition U1>U2< fulfilled
222.2028 Sync. U1< U2>
OUT
Sync. Condition U1<U2> fulfilled
222.2029 Sync. U1< U2<
OUT
Sync. Condition U1<U2< fulfilled
222.2030 Sync. Udiff ok
OUT
Sync. Voltage difference (Udiff) okay
222.2031 Sync. fdiff ok
OUT
Sync. Frequency difference (fdiff) okay
222.2032 Sync. α ok
OUT
Sync. Angle difference (adiff) okay
222.2033 Sync. f1>>
OUT
Sync. Frequency f1 > fmax permissible
222.2034 Sync. f1<<
OUT
Sync. Frequency f1 < fmin permissible
222.2035 Sync. f2>>
OUT
Sync. Frequency f2 > fmax permissible
222.2036 Sync. f2<<
OUT
Sync. Frequency f2 < fmin permissible
222.2037 Sync. U1>>
OUT
Sync. Voltage U1 > Umax permissible
222.2038 Sync. U1<<
OUT
Sync. Voltage U1 < Umin permissible
222.2039 Sync. U2>>
OUT
Sync. Voltage U2 > Umax permissible
222.2040 Sync. U2<<
OUT
Sync. Voltage U2 < Umin permissible
222.2090 Sync U2>U1
OUT
Sync. Udiff too large (U2>U1)
222.2091 Sync U2<U1
OUT
Sync. Udiff too large (U2<U1)
222.2092 Sync f2>f1
OUT
Sync. fdiff too large (f2>f1)
222.2093 Sync f2<f1
OUT
Sync. fdiff too large (f2<f1)
222.2094 Sync α2>α1
OUT
Sync. alphadiff too large (a2>a1)
222.2095 Sync α2<α1
OUT
Sync. alphadiff too large (a2<a1)
222.2102 >BLK Sync CLOSE
SP
>BLOCK Sync. CLOSE command
222.2103 Sync. CLOSE BLK
OUT
Sync. CLOSE command is BLOCKED
222.2302 Sync synchron 1
OUT
Sync. Synchronization condition 1 okay
222.2303 Sync synchron 2
OUT
Sync. Synchronization condition 2 okay
222.2309 Sync sup.asym.
OUT
Sync-supervision U1,U2 asymmetrical
222.2310 Sync sup. α
OUT
Sync-supervision Alpha>
222.2332 Sync f syn 1
OUT
Sync:Synchronization cond. f1
222.2333 Sync f syn 2
OUT
Sync:Synchronization cond. f2
222.2334 Sync Stop TS
OUT
Sync:Stop by invalid TapChangerVal.
222.2335 SyncSEQ U1 123
OUT
Sync: U1 phase sequence is L1 L2 L3
222.2336 SyncSEQ U1 132
OUT
Sync: U1 phase sequence is L1 L3 L2
222.2337 SyncSEQ U2 123
OUT
Sync: U2 phase sequence is L1 L2 L3
222.2338 SyncSEQ U2 132
OUT
Sync: U2 phase sequence is L1 L3 L2
2.2.3.2
2.2.3.3
Functions
2.2 Paralleling Functions
SIPROTEC 4, 7VE61 and 7VE63, Manual
79
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...