Figure 2-46
Logic Diagram of the Vector Jump Detection
Setting Notes
General
The vector jump protection is only effective and available if address 146
VECTOR JUMP
is set to
Enabled
during configuration.
Address 4601
VECTOR JUMP
serves to switch the function
ON
or
OFF
or to block only the trip command
(
Block relay
).
Pickup Values
The value to be set for the vector jump (address 4602
DELTA PHI
) depends on the feed and load conditions.
Abrupt active power changes cause a jump of the voltage vector. The value to be set must be established in
accordance with the particular power system. This can be done on the basis of the simplified equivalent circuit
of the diagram “Voltage Vector after a Load Shedding” in the Functional Description section, or using network
calculation software.
If a setting is too sensitive, the protection function is likely to perform a network decoupling every time loads
are connected or disconnected. Therefore the default setting is
10°
.
The admissible voltage operating range can be set at addresses 4605 für
U MIN
and 4606 für
U MAX
. Setting
range limits are to some extent a matter of the utility's policy. The value for
U MIN
should be below the
admissible level of short voltage dips for which network decoupling is desired. The default setting is
80 %
of
the nominal voltage. For U MAX the maximum admissible voltage must be selected. This will be in most cases
130 %
of the nominal voltage
Time Delays
The time delay
T DELTA PHI
(address 4603) should be left at zero, unless you wish to transmit the trip indi-
cation with a delay to a logic (CFC), or to leave enough time for an external blocking to take effect.
2.8.2
Functions
2.8 Jump of Voltage Vector
SIPROTEC 4, 7VE61 and 7VE63, Manual
99
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...