8
Feldbus (DNP, Modbus)
External synchronization using field bus
9
NTP (IEC 61850)
External synchronization using system interface (IEC 61850)
Either the European time format (DD.MM.YYYY) or the US format (MM/DD/YYYY) can be specified for the
device display
To preserve the internal battery, this switches off automatically after some hours in the absence of an auxiliary
voltage supply.
Commissioning Aids
Device data sent to a central or master computer system during test mode or commissioning can be influ-
enced. There are tools for testing the system interface and the binary inputs and outputs of the device.
Applications
•
Prerequisites
•
Commissioning
Prerequisites
The following applies to the utilization of the commissioning aids as described below:
The device must be equipped with an interface.
The device has to be connected to a control center.
Functional Description
Test Messages to the SCADA Interface during Test Operation
If the device is connected to a central or main computer system via the SCADA interface, then the information
that is transmitted can be influenced.
Depending on the type of protocol, all messages and measured values transferred to the central control
system can be identified with an added message “test operation”-bit while the device is being tested on site
(test mode). This identification prevents the messages from being incorrectly interpreted as resulting from an
actual power system disturbance or event. As another option, all messages and measured values normally
transferred via the system interface can be blocked during the testing (“block data transmission”).
Data transmission block can be accomplished by controlling binary inputs, by using the operating panel on the
device, or with a PC and DIGSI via the operator interface.
The SIPROTEC 4 System Description describes how to activate and deactivate test mode and blocked data
transmission.
Checking the System Interface
If the device features a system interface and uses it to communicate with the control centre, the DIGSI device
operation can be used to test if indications are transmitted correctly.
A dialog box displays the texts of all annunciations that have been masked to the system interface in the
matrix. In another column of the dialog box you can specify a value for the annunciations that you want to
test (e.g. coming/ going)to generate an annunciation as soon as you have entered password no. 6 (for hard-
ware test menus). The annunciation is output and can no
The procedure is described in detail in Chapter Mounting and Commissioning.
Checking the Binary Inputs and Outputs
The binary inputs, outputs, and LEDs of a SIPROTEC 4 device can be individually controlled. This feature can
be, for example, to verify control wiring from the device to substation equipment (operational checks), during
commissioning.
A dialog box displays all binary inputs and outputs existing in the device, and the LEDs with their current state.
It also shows which commands or annunciations are masked to which hardware component. In another
2.14.10
2.14.10.1
Functions
2.14 Auxiliary Functions
SIPROTEC 4, 7VE61 and 7VE63, Manual
129
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...