Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
Addr.
Parameter
Function
Setting Options
Default Setting
Comments
270
Rated Frequency
P.System Data 1 50 Hz
60 Hz
16,7 Hz
50 Hz
Rated Frequency
280
TMin TRIP CMD
P.System Data 1 0.01 .. 32.00 sec
0.15 sec
Minimum TRIP Command
Duration
302
CHANGE
Change Group
Group A
Group B
Group C
Group D
Binary Input
Protocol
Group A
Change to Another Setting
Group
401
WAVEFORM-
TRIGGER
Osc. Fault Rec.
Save w. Pickup
Save w. TRIP
Start w. TRIP
Start w. TRIP
Waveform Capture
403
MAX. LENGTH
Osc. Fault Rec.
0.30 .. 10.00 sec
10.00 sec
Max. length of a Waveform
Capture Record
404
PRE. TRIG. TIME
Osc. Fault Rec.
0.05 .. 5.00 sec
5.00 sec
Captured Waveform Prior to
Trigger
405
POST REC. TIME
Osc. Fault Rec.
0.05 .. 2.00 sec
2.00 sec
Captured Waveform after
Event
406
BinIn CAPT.TIME
Osc. Fault Rec.
0.10 .. 10.00 sec
10.00 sec
Capture Time via Binary
Input
610
FltDisp.LED/LCD
Device
Target on PU
Target on TRIP
Target on PU
Fault Display on LED / LCD
615
T MIN LED HOLD
Device
0 .. 60 min
5 min
Minimum hold time of
latched LEDs
640
Start image DD
Device
image 1
image 2
image 3
image 4
image 1
Start image Default Display
4001
UNDERVOLTAGE
Undervoltage
OFF
ON
Block relay
OFF
Undervoltage Protection
4002
U<
Undervoltage
10.0 .. 125.0 V
75.0 V
U< Pickup
4003
T U<
Undervoltage
0.00 .. 60.00 sec
3.00 sec
T U< Time Delay
4004
U<<
Undervoltage
10.0 .. 125.0 V
65.0 V
U<< Pickup
4005
T U<<
Undervoltage
0.00 .. 60.00 sec
0.50 sec
T U<< Time Delay
4006A U< DOUT RATIO
Undervoltage
1.01 .. 1.20
1.05
U<, U<< Drop Out Ratio
4007
MEAS. INPUT
Undervoltage
Ua
Ub
Uc
Ud
Ue
Uf
Ua
Used Measuring Input
E.2
Functions, Settings, Information
E.2 Settings
260
SIPROTEC 4, 7VE61 and 7VE63, Manual
C53000-G1176-C163-3, Edition 10.2017
Summary of Contents for SIPROTEC 4 7VE61
Page 8: ...8 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 24: ...24 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 142: ...142 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 192: ...192 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 222: ...222 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 230: ...230 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 256: ...256 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 314: ...314 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 316: ...316 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...
Page 330: ...330 SIPROTEC 4 7VE61 and 7VE63 Manual C53000 G1176 C163 3 Edition 10 2017 ...