[logikdia-ueberspgschutz-u2-spggegsys-wlk-280802, 1, en_GB]
Figure 2-27
Logic diagram of the overvoltage protection for the negative sequence voltage system U
2
The overvoltage protection for the negative sequence system can also be blocked via a binary input
>U2>(>)
BLK
. The stages of the negative sequence voltage protection are automatically blocked as soon as an asym-
metrical voltage failure was detected (“Fuse-Failure-Monitor”, also see Section
for voltage transformers has been signalled via the binary input
>FAIL:Feeder VT
.
During the single-pole dead time, the stages of the negative-sequence overvoltage protection are automati-
cally blocked since the occurring negative sequence values are only influenced by the asymmetrical power
flow, not by the fault in the system. If the device cooperates with an external automatic reclosure function, or
if a singlepole tripping can be triggered by a different protection system (working in parallel), the overvoltage
protection for the negative sequence system must be blocked via a binary input during single-pole tripping.
Please bear in mind that the device is designed for a three-phase voltage connection. Single-phase connection
is also possible but no adjustments have been made in this respect. This must be taken into consideration
when setting the pickup value.
Overvoltage zero-sequence system 3U
0
depicts the logic diagram of the zero-sequence voltage stage. The fundamental component is
numerically filtered from the measuring voltage so that the harmonics or transient voltage peaks remain
largely eliminated.
The triple zero-sequence voltage 3·U
0
is fed to the two threshold stages
3U0>
(address 3722) and
3U0>>
(address 3724). Combined with the associated time delays
T 3U0>
(address 3723) and
T 3U0>>
(address
3725), these stages form a two-stage overvoltage protection for the zero-sequence system. Here too, the
dropout to pickup ratio can be set (
3U0>(>) RESET
, address
3U0>(>) RESET
). Furthermore, a restraint
delay can be configured which is implemented by repeated measuring (approx. 3 periods).
The overvoltage protection for the zero-sequence system can also be blocked via a binary input
>3U0>(>)
BLK
. The stages of the zero-sequence voltage protection are automatically blocked as soon as an asymmetrical
voltage failure was detected (“Fuse-Failure-Monitor”, also see Section
Functions
2.5 Under and over-voltage protection (optional)
100
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...