φB
must be at least 3° apart. Incorrect parameter settings cause the indication 132
φ Set wrong
to be
output.
Settings
Addresses which have an appended “A” can only be changed with DIGSI, under “Additional Settings”.
The table indicates region-specific presettings. Column C (configuration) indicates the corresponding secon-
dary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
2901
MEASURE. SUPERV
ON
OFF
ON
Measurement Supervision
2902A
BALANCE U-LIMIT
10 .. 100 V
50 V
Voltage Threshold for
Balance Monitoring
2903A
BAL. FACTOR U
0.58 .. 0.95
0.75
Balance Factor for Voltage
Monitor
2904A
BALANCE I LIMIT
1A
0.10 .. 1.00 A
0.50 A
Current Balance Monitor
5A
0.50 .. 5.00 A
2.50 A
2905A
BAL. FACTOR I
0.10 .. 0.95
0.50
Balance Factor for Current
Monitor
2906A
ΣI THRESHOLD
1A
0.05 .. 2.00 A
0.10 A
Summated Current Moni-
toring Threshold
5A
0.25 .. 10.00 A
0.50 A
2907A
ΣI FACTOR
0.00 .. 0.95
0.10
Summated Current Moni-
toring Factor
2908A
T BAL. U LIMIT
5 .. 100 sec
5 sec
T Balance Factor for
Voltage Monitor
2909A
T BAL. I LIMIT
5 .. 100 sec
5 sec
T Current Balance Monitor
2910
FUSE FAIL MON.
ON
OFF
ON
Fuse Failure Monitor
2911A
FFM U>(min)
10 .. 100 V
30 V
Minimum Voltage
Threshold U>
2912A
FFM I< (max)
1A
0.10 .. 1.00 A
0.10 A
Maximum Current
Threshold I<
5A
0.50 .. 5.00 A
0.50 A
2913A
FFM U<max (3ph)
2 .. 100 V
15 V
Maximum Voltage
Threshold U< (3phase)
2914A
FFM Idelta (3p)
1A
0.05 .. 1.00 A
0.10 A
Delta Current Threshold
(3phase)
5A
0.25 .. 5.00 A
0.50 A
2915
V-Supervision
w/ CURR.SUP
w/ I> & CBaux
OFF
w/ CURR.SUP
Voltage Failure Supervision
2916A
T V-Supervision
0.00 .. 30.00 sec
3.00 sec
Delay Voltage Failure
Supervision
2941
φA
0 .. 359 °
200 °
Limit setting PhiA
2942
φB
0 .. 359 °
340 °
Limit setting PhiB
2943
I1>
1A
0.05 .. 2.00 A
0.05 A
Minimum value I1>
5A
0.25 .. 10.00 A
0.25 A
2944
U1>
2 .. 70 V
20 V
Minimum value U1>
2.7.1.7
Functions
2.7 Monitoring Functions
SIPROTEC 4, 7VK61, Manual
143
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...