Information List
No.
Information
Type of
Informa-
tion
Comments
130
φ(PQ Pos. Seq.)
OUT
Load angle Phi(PQ Positive sequence)
131
φ(PQ Pos) block
OUT
Load angle Phi(PQ) blocked
132
φ Set wrong
OUT
Setting error: |PhiA - PhiB| < 3°
161
Fail I Superv.
OUT
Failure: General Current Supervision
162
Failure Σ I
OUT
Failure: Current Summation
163
Fail I balance
OUT
Failure: Current Balance
164
Fail U Superv.
OUT
Failure: General Voltage Supervision
165
Fail Σ U Ph-E
OUT
Failure: Voltage summation Phase-Earth
167
Fail U balance
OUT
Failure: Voltage Balance
168
Fail U absent
OUT
Failure: Voltage absent
169
VT FuseFail>10s
OUT
VT Fuse Failure (alarm >10s)
170
VT FuseFail
OUT
VT Fuse Failure (alarm instantaneous)
171
Fail Ph. Seq.
OUT
Failure: Phase Sequence
195
Fail Conductor
OUT
Failure: Broken Conductor
196
Fuse Fail M.OFF
OUT
Fuse Fail Monitor is switched OFF
197
MeasSup OFF
OUT
Measurement Supervision is switched OFF
Trip circuit supervision
Functional Description
Trip Circuit Supervision
The 7VK61 incorporates an integrated trip circuit supervision function. Depending on the number of available
binary inputs (not connected to a common potential), supervision with one or two binary inputs can be
selected. If the routing of the required binary inputs does not comply with the selected supervision mode, an
alarm is issued (“TripC ProgFAIL”) with identification of the non-compliant circuit. When using two binary
inputs, malfunctions in the trip circuit can be detected under all circuit breaker conditions. When only one
binary input is used, malfunctions in the circuit breaker itself cannot be detected. If single-pole tripping is
possible, a separate trip circuit supervision can be implemented for each circuit breaker pole provided the
required binary inputs are available.
These which for the two binary inputs use binary inputs must have no common potential. Therefore, it must
be ensured the use of external measures for the galvanic separation.
Supervision with Two Binary Inputs
When using two binary inputs, these are connected according to
parallel to the associated trip
contact on one side, and parallel to the circuit breaker auxiliary contacts on the other.
A precondition for the use of the trip circuit supervision is that the control voltage for the circuit breaker is
higher than the total of the minimum voltages drops at the two binary inputs (U
Ctrl
> 2·U
BImin
). Since at least 19
V are needed for each binary input, the supervision function can only be used with a system control voltage of
over 38 V.
2.7.1.8
2.7.2
2.7.2.1
Functions
2.7 Monitoring Functions
144
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...