Test voltage
500 V; 50 Hz
Transmission rate
min. 4800 Baud, max. 38400 Baud
Factory setting 19200 Baud
Transmission distance
max. 15 m
RS485
Connection for flush-mounted housing rear panel, slot “B”,
9-pole D-subminiature female connector
Connection for surface-mounted
housing
at the bottom side of the console housing
9-pole D-subminiature female connector
Test voltage
500 V; 50 Hz
Transmission rate
min. 4800 Baud, max. 38400 Baud
Factory setting 19200 Baud
Transmission distance
max. 1 km
Optical fibre cable (FO
FO connector type
ST connector
Connection for flush-mounted housing rear panel, slot “B”
Connection for surface-mounted
housing
at bottom side of the console housing
Optical wavelength
λ = 820 nm
Laser class 1 according to EN
60825-1/-2
Using glass fiber 50/125 μm or
Using glass fibre 62.5/125 μm
Permissible optical signal attenuation
Max. 8 dB, with glass fibre 62.5/125 μm
Maximum transmission distance
max. 1.5 km
Character idle state
Selectable, factory setting“Light off”
Profibus RS485 (FMS and DP)
Connection for flush-mounted housing rear panel, slot “B”,
9-pole D-subminiature female connector
Connection for surface-mounted
housing
at the bottom side of the console housing
9-pole D-subminiature female connector
Test voltage
500 V; 50 Hz
Transmission rate
bis 12 MBaud
Transmission distance
1000 m at ≤ 93.75 kBaud
500 m at ≤ 187.5 kBaud
200 m at ≤ 1.5 MBaud
100 m at ≤ 12 MBaud
Profibus FO (FMS and DP)
FO connector type
ST connector single ring / double ring
FMS: depending on ordered version;
DP: only double ring available
Connection for flush-mounted housing rear panel, slot “B”
Connection for surface-mounted
housing
Please use the version with Profibus RS485 in the console housing and a sepa-
rate electrical/ optical converter.
Transmission rate
Conversion by means of external OLM up to 1.5 MBaud
≥ 500 kBaud for normal version
≤ 57600 Baud with detached operator panel
Recommended transmission rate:
> 500 kBaud
Optical wavelength
λ = 820 nm
Laser class 1 according to EN
60825-1/-2
Using glass fiber 50/125 μm or
Using glass fibre 62.5/125 μm
Technical Data
4.1 General
SIPROTEC 4, 7VK61, Manual
229
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...