Addr.
Parameter
Setting Options
Default Setting
Comments
106
VT CONNECTION
3phase
1phase
NO
3phase
Voltage transformer connection
107
CT CONNECTION
YES
NO
YES
Current transformer connection
110
Trip mode
3pole only
1-/3pole
3pole only
Trip mode
126
Back-Up O/C
Disabled
TOC IEC
TOC ANSI
TOC IEC /w 3ST
Disabled
Backup overcurrent
133
Auto Reclose
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
Disabled
Disabled
Auto-Reclose Function
134
AR control mode
Pickup w/ Tact
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
Trip w/ Tact
Auto-Reclose control mode
135
Synchro-Check
Disabled
Enabled
Disabled
Synchronism and Voltage Check
137
U/O VOLTAGE
Disabled
Enabled
Disabled
Under / Overvoltage Protection
139
BREAKER FAILURE
Disabled
Enabled
enabled w/ 3I0>
Disabled
Breaker Failure Protection
140
Trip Cir. Sup.
Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Disabled
Trip Circuit Supervision
Device
The device requires some general information. This may be, for example, the type of indication to be issued in
the event a power system fault occurs.
Trip-Dependent Indications
Spontaneous Fault Messages
After a fault, the essential fault data spontaneously appear on the device display. Under address 610
FltDisp.LED/LCD
you can select whether the spontaneous fault indications are updated in every case of
fault (
Target on PU
) or only in faults with tripping (
Target on TRIP
).
2.1.2
2.1.2.1
Functions
2.1 General
28
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...