201
CT Starpoint
P.System Data
1
towards Line
towards Busbar
towards Line
CT Starpoint
203
Unom PRIMARY
P.System Data
1
1.0 .. 1200.0 kV
400.0 kV
Rated Primary Voltage
204
Unom SECONDARY P.System Data
1
80 .. 125 V
100 V
Rated Secondary Voltage
(Ph-Ph)
205
CT PRIMARY
P.System Data
1
10 .. 5000 A
1000 A
CT Rated Primary Current
206
CT SECONDARY
P.System Data
1
1A
5A
1A
CT Rated Secondary
Current
207
SystemStarpoint
P.System Data
1
Solid Earthed
Peterson-Coil
Isolated
Solid Earthed
System Starpoint is
210
U4 transformer
P.System Data
1
Not connected
Udelta transf.
Usy2 transf.
Ux transformer
Not connected
U4 voltage transformer is
211
Uph / Udelta
P.System Data
1
0.10 .. 9.99
1.73
Matching ratio Phase-VT
To Open-Delta-VT
212
Usy2 connection
P.System Data
1
L1-E
L2-E
L3-E
L1-L2
L2-L3
L3-L1
L1-L2
VT connection for Usy2
214A φ Usy2-Usy1
P.System Data
1
0 .. 360 °
0 °
Angle adjustment Usy2-
Usy1
215
Usy1/Usy2 ratio
P.System Data
1
0.50 .. 2.00
1.00
Matching ratio Usy1 /
Usy2
220
I4 transformer
P.System Data
1
Not connected
In prot. line
In prot. line
I4 current transformer is
221
I4/Iph CT
P.System Data
1
0.010 .. 5.000
1.000
Matching ratio I4/Iph for
CT's
230
Rated Frequency
P.System Data
1
50 Hz
60 Hz
50 Hz
Rated Frequency
235
PHASE SEQ.
P.System Data
1
L1 L2 L3
L1 L3 L2
L1 L2 L3
Phase Sequence
239
T-CB close
P.System Data
1
0.01 .. 0.60 sec
0.06 sec
Closing (operating) time
of CB
240A TMin TRIP CMD
P.System Data
1
0.02 .. 30.00 sec
0.10 sec
Minimum TRIP Command
Duration
241A TMax CLOSE CMD
P.System Data
1
0.01 .. 30.00 sec
0.10 sec
Maximum Close
Command Duration
E.2
Functions, Settings, Information
E.2 Settings
SIPROTEC 4, 7VK61, Manual
287
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...