Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
2660 IEC Curve
Back-Up O/C
Normal Inverse
Very Inverse
Extremely Inv.
LongTimeInverse
Normal Inverse
IEC Curve
2661 ANSI Curve
Back-Up O/C
Inverse
Short Inverse
Long Inverse
Moderately Inv.
Very Inverse
Extremely Inv.
Definite Inv.
Inverse
ANSI Curve
2670 I(3I0)p Tele/BI
Back-Up O/C
NO
YES
NO
Instantaneous trip via
Teleprot./BI
2671 I(3I0)p SOTF
Back-Up O/C
NO
YES
NO
Instantaneous trip after
SwitchOnToFault
2680 SOTF Time DELAY
Back-Up O/C
0.00 .. 30.00 sec
0.00 sec
Trip time delay after SOTF
2901 MEASURE. SUPERV Meas-
urem.Superv
ON
OFF
ON
Measurement Supervision
2902A BALANCE U-LIMIT
Meas-
urem.Superv
10 .. 100 V
50 V
Voltage Threshold for
Balance Monitoring
2903A BAL. FACTOR U
Meas-
urem.Superv
0.58 .. 0.95
0.75
Balance Factor for
Voltage Monitor
2904A BALANCE I LIMIT
Meas-
urem.Superv
1A
0.10 .. 1.00 A
0.50 A
Current Balance Monitor
5A
0.50 .. 5.00 A
2.50 A
2905A BAL. FACTOR I
Meas-
urem.Superv
0.10 .. 0.95
0.50
Balance Factor for Current
Monitor
2906A ΣI THRESHOLD
Meas-
urem.Superv
1A
0.05 .. 2.00 A
0.10 A
Summated Current Moni-
toring Threshold
5A
0.25 .. 10.00 A
0.50 A
2907A ΣI FACTOR
Meas-
urem.Superv
0.00 .. 0.95
0.10
Summated Current Moni-
toring Factor
2908A T BAL. U LIMIT
Meas-
urem.Superv
5 .. 100 sec
5 sec
T Balance Factor for
Voltage Monitor
2909A T BAL. I LIMIT
Meas-
urem.Superv
5 .. 100 sec
5 sec
T Current Balance
Monitor
2910 FUSE FAIL MON.
Meas-
urem.Superv
ON
OFF
ON
Fuse Failure Monitor
2911A FFM U>(min)
Meas-
urem.Superv
10 .. 100 V
30 V
Minimum Voltage
Threshold U>
2912A FFM I< (max)
Meas-
urem.Superv
1A
0.10 .. 1.00 A
0.10 A
Maximum Current
Threshold I<
5A
0.50 .. 5.00 A
0.50 A
2913A FFM U<max (3ph)
Meas-
urem.Superv
2 .. 100 V
15 V
Maximum Voltage
Threshold U< (3phase)
2914A FFM Idelta (3p)
Meas-
urem.Superv
1A
0.05 .. 1.00 A
0.10 A
Delta Current Threshold
(3phase)
5A
0.25 .. 5.00 A
0.50 A
2915 V-Supervision
Meas-
urem.Superv
w/ CURR.SUP
w/ I> & CBaux
OFF
w/ CURR.SUP
Voltage Failure Supervi-
sion
2916A T V-Supervision
Meas-
urem.Superv
0.00 .. 30.00 sec
3.00 sec
Delay Voltage Failure
Supervision
Functions, Settings, Information
E.2 Settings
290
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...