Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
2941 φA
Meas-
urem.Superv
0 .. 359 °
200 °
Limit setting PhiA
2942 φB
Meas-
urem.Superv
0 .. 359 °
340 °
Limit setting PhiB
2943 I1>
Meas-
urem.Superv
1A
0.05 .. 2.00 A
0.05 A
Minimum value I1>
5A
0.25 .. 10.00 A
0.25 A
2944 U1>
Meas-
urem.Superv
2 .. 70 V
20 V
Minimum value U1>
3401 AUTO RECLOSE
Autoreclosure
OFF
ON
ON
Auto-Reclose function
3402 CB? 1.TRIP
Autoreclosure
YES
NO
NO
CB ready interrogation at
1st trip
3403 T-RECLAIM
Autoreclosure
0.50 .. 300.00 sec
3.00 sec
Reclaim time after
successful AR cycle
3403 T-RECLAIM
Autoreclosure
0.50 .. 300.00 sec
3.00 sec
Reclaim time after
successful AR cycle
3404 T-BLOCK MC
Autoreclosure
0.50 .. 300.00 sec
1.00 sec
AR blocking duration after
manual close
3406 EV. FLT. RECOG.
Autoreclosure
with PICKUP
with TRIP
with TRIP
Evolving fault recognition
3407 EV. FLT. MODE
Autoreclosure
blocks AR
starts 3p AR
starts 3p AR
Evolving fault (during the
dead time)
3408 T-Start MONITOR
Autoreclosure
0.01 .. 300.00 sec
0.20 sec
AR start-signal monitoring
time
3409 CB TIME OUT
Autoreclosure
0.01 .. 300.00 sec
3.00 sec
Circuit Breaker (CB)
Supervision Time
3410 T RemoteClose
Autoreclosure
0.00 .. 300.00 sec
2147483647 sec
Send delay for remote
close command
3411A T-DEAD EXT.
Autoreclosure
0.50 .. 300.00 sec
2147483647 sec
Maximum dead time
extension
3425 AR w/ BackUpO/C
Autoreclosure
YES
NO
YES
AR with back-up overcur-
rent
3430 AR TRIP 3pole
Autoreclosure
Autoreclosure
YES
NO
YES
3pole TRIP by AR
3431 DLC or RDT
Autoreclosure
WITHOUT
RDT
DLC
WITHOUT
Dead Line Check or
Reduced Dead Time
3433 T-ACTION ADT
Autoreclosure
0.01 .. 300.00 sec
0.20 sec
Action time
3434 T-MAX ADT
Autoreclosure
0.50 .. 3000.00 sec 5.00 sec
Maximum dead time
3435 ADT 1p allowed
Autoreclosure
YES
NO
NO
1pole TRIP allowed
3436 ADT CB? CLOSE
Autoreclosure
YES
NO
NO
CB ready interrogation
before reclosing
3437 ADT SynRequest
Autoreclosure
YES
NO
NO
Request for synchro-
check after 3pole AR
3438 T U-stable
Autoreclosure
Autoreclosure
0.10 .. 30.00 sec
0.10 sec
Supervision time for
dead/ live voltage
3440 U-live>
Autoreclosure
Autoreclosure
30 .. 90 V
48 V
Voltage threshold for live
line or bus
Functions, Settings, Information
E.2 Settings
SIPROTEC 4, 7VK61, Manual
291
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...