Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
3771 U1<(<)
Voltage Prot.
OFF
Alarm Only
ON
U<Alarm U<<Trip
OFF
Operating mode U1
undervoltage prot.
3772 U1<
Voltage Prot.
1.0 .. 100.0 V
30.0 V
U1< Pickup
3773 T U1<
Voltage Prot.
0.00 .. 100.00 sec
2.00 sec
T U1< Time Delay
3774 U1<<
Voltage Prot.
1.0 .. 100.0 V
10.0 V
U1<< Pickup
3775 T U1<<
Voltage Prot.
0.00 .. 100.00 sec
1.00 sec
T U1<< Time Delay
3778 CURR.SUP.U1<
Voltage Prot.
ON
OFF
ON
Current supervision (U1)
3779A U1<(<) RESET
Voltage Prot.
1.01 .. 1.20
1.05
U1<(<) Reset ratio
3901 FCT BreakerFail
Breaker Failure
ON
OFF
ON
Breaker Failure Protection
3902 I> BF
Breaker Failure 1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold I>
5A
0.25 .. 100.00 A
0.50 A
3903 1p-RETRIP (T1)
Breaker Failure
NO
YES
YES
1pole retrip with stage T1
(local trip)
3904 T1-1pole
Breaker Failure
0.00 .. 30.00 sec
0.00 sec
T1, Delay after 1pole start
(local trip)
3905 T1-3pole
Breaker Failure
0.00 .. 30.00 sec
0.00 sec
T1, Delay after 3pole start
(local trip)
3906 T2
Breaker Failure
0.00 .. 30.00 sec
0.15 sec
T2, Delay of 2nd stage
(busbar trip)
3907 T3-BkrDefective
Breaker Failure
0.00 .. 30.00 sec
0.00 sec
T3, Delay for start with
defective bkr.
3908 Trip BkrDefect.
Breaker Failure
NO
with T1-trip
with T2-trip
w/ T1/T2-trip
NO
Trip output selection with
defective bkr
3909 Chk BRK CONTACT Breaker Failure
NO
YES
YES
Check Breaker contacts
3912 3I0> BF
Breaker Failure 1A
0.05 .. 20.00 A
0.10 A
Pick-up threshold 3I0>
5A
0.25 .. 100.00 A
0.50 A
3913 T2StartCriteria
Breaker Failure
With exp. of T1
Parallel withT1
Parallel withT1
T2 Start Criteria
3921 End Flt. stage
Breaker Failure
ON
OFF
OFF
End fault protection
3922 T-EndFault
Breaker Failure
0.00 .. 30.00 sec
2.00 sec
Trip delay of end fault
protection
3931 PoleDiscrepancy
Breaker Failure
ON
OFF
OFF
Pole Discrepancy supervi-
sion
3932 T-PoleDiscrep.
Breaker Failure
0.00 .. 30.00 sec
2.00 sec
Trip delay with pole
discrepancy
4001 FCT TripSuperv.
TripCirc.Superv
ON
OFF
OFF
TRIP Circuit Supervision is
4002 No. of BI
TripCirc.Superv
1 .. 2
2
Number of Binary Inputs
per trip circuit
4003 Alarm Delay
TripCirc.Superv
1 .. 30 sec
2 sec
Delay Time for alarm
Functions, Settings, Information
E.2 Settings
296
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...