Addr. Parameter
Function
C
Setting Options
Default Setting
Comments
3437 ADT SynRequest
Autoreclosure
YES
NO
NO
Request for synchro-
check after 3pole AR
3438 T U-stable
Autoreclosure
Autoreclosure
0.10 .. 30.00 sec
0.10 sec
Supervision time for
dead/live voltage
3440 U-live>
Autoreclosure
Autoreclosure
30 .. 90 V
48 V
Voltage threshold for live
line or bus
3441 U-dead<
Autoreclosure
Autoreclosure
2 .. 70 V
30 V
Voltage threshold for
dead line
3450 1.AR: START
Autoreclosure
YES
NO
YES
AR start allowed in this
cycle?
3451 1.AR: T-ACTION
Autoreclosure
0.01 .. 300.00 sec
0.20 sec
Action time
3453 1.AR Tdead 1Flt
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Dead time after 1phase
faults
3454 1.AR Tdead 2Flt
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Dead time after 2phase
faults
3455 1.AR Tdead 3Flt
Autoreclosure
0.01 .. 1800.00 sec 0.50 sec
Dead time after 3phase
faults
3456 1.AR Tdead1Trip
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Dead time after 1pole trip
3457 1.AR Tdead3Trip
Autoreclosure
0.01 .. 1800.00 sec 0.50 sec
Dead time after 3pole trip
3458 1.AR: Tdead EV.
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Dead time after evolving
fault
3459 1.AR: CB? CLOSE
Autoreclosure
YES
NO
NO
CB ready interrogation
before reclosing
3460 1.AR SynRequest
Autoreclosure
YES
NO
NO
Request for synchro-
check after 3pole AR
3461 2.AR: START
Autoreclosure
YES
NO
NO
AR start allowed in this
cycle?
3462 2.AR: T-ACTION
Autoreclosure
0.01 .. 300.00 sec
0.20 sec
Action time
3464 2.AR Tdead 1Flt
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Dead time after 1phase
faults
3465 2.AR Tdead 2Flt
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Dead time after 2phase
faults
3466 2.AR Tdead 3Flt
Autoreclosure
0.01 .. 1800.00 sec 0.50 sec
Dead time after 3phase
faults
3467 2.AR Tdead1Trip
Autoreclosure
0.01 .. 1800.00 sec 2147483647 sec
Dead time after 1pole trip
3468 2.AR Tdead3Trip
Autoreclosure
0.01 .. 1800.00 sec 0.50 sec
Dead time after 3pole trip
3469 2.AR: Tdead EV.
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Dead time after evolving
fault
3470 2.AR: CB? CLOSE
Autoreclosure
YES
NO
NO
CB ready interrogation
before reclosing
3471 2.AR SynRequest
Autoreclosure
YES
NO
NO
Request for synchro-
check after 3pole AR
3472 3.AR: START
Autoreclosure
YES
NO
NO
AR start allowed in this
cycle?
3473 3.AR: T-ACTION
Autoreclosure
0.01 .. 300.00 sec
0.20 sec
Action time
3475 3.AR Tdead 1Flt
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Dead time after 1phase
faults
3476 3.AR Tdead 2Flt
Autoreclosure
0.01 .. 1800.00 sec 1.20 sec
Dead time after 2phase
faults
Functions, Settings, Information
E.2 Settings
302
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...