No.
Information
Type of
Informa-
tion
Comments
68
Clock SyncError
OUT
Clock Synchronization Error
69
DayLightSavTime
OUT
Daylight Saving Time
70
Settings Calc.
OUT
Setting calculation is running
71
Settings Check
OUT
Settings Check
72
Level-2 change
OUT
Level-2 change
73
Local change
OUT
Local setting change
110
Event Lost
OUT_Ev
Event lost
113
Flag Lost
OUT
Flag Lost
125
Chatter ON
OUT
Chatter ON
126
ProtON/OFF
IntSP
Protection ON/OFF (via system port)
127
AR ON/OFF
IntSP
Auto Reclose ON/OFF (via system port)
140
Error Sum Alarm
OUT
Error with a summary alarm
144
Error 5V
OUT
Error 5V
160
Alarm Sum Event
OUT
Alarm Summary Event
177
Fail Battery
OUT
Failure: Battery empty
181
Error A/D-conv.
OUT
Error: A/D converter
183
Error Board 1
OUT
Error Board 1
184
Error Board 2
OUT
Error Board 2
185
Error Board 3
OUT
Error Board 3
186
Error Board 4
OUT
Error Board 4
187
Error Board 5
OUT
Error Board 5
188
Error Board 6
OUT
Error Board 6
189
Error Board 7
OUT
Error Board 7
190
Error Board 0
OUT
Error Board 0
191
Error Offset
OUT
Error: Offset
192
Error1A/5Awrong
OUT
Error:1A/5Ajumper different from setting
193
Alarm adjustm.
OUT
Alarm: Analog input adjustment invalid
194
Error neutralCT
OUT
Error: Neutral CT different from MLFB
320
Warn Mem. Data
OUT
Warn: Limit of Memory Data exceeded
321
Warn Mem. Para.
OUT
Warn: Limit of Memory Parameter exceeded
322
Warn Mem. Oper.
OUT
Warn: Limit of Memory Operation exceeded
323
Warn Mem. New
OUT
Warn: Limit of Memory New exceeded
Power System Data 1
The device requires some plant and power system data in order to be able to adapt its functions accordingly,
depending on the actual application. The data required include for instance rated data of the substation and
the measuring transformers, polarity and connection of the measured quantities, if necessary features of the
circuit breakers, and others. Furthermore, there are several function parameters associated with several func-
tions rather than one specific protection, control or monitoring function. The Power System Data 1 can only be
changed from a PC running DIGSI and are discussed in this section.
2.1.3
Functions
2.1 General
SIPROTEC 4, 7VK61, Manual
31
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...