Table 2-4
Trip signals of the single phases
Internal Indication
Figure
Output Indication
No.
Ι
>> OFF L1
Ι
> OFF L1
Ι
p OFF L1
Ι
>>> OFF L1
O/C TRIP 1p.L1
or
O/C TRIP L123
7212 or
7215
Ι
>> OFF L2
Ι
> OFF L2
Ι
p OFF L2
Ι
>>> OFF L2
O/C TRIP 1p.L2
or
O/C TRIP L123
7213 or
7215
Ι
>> OFF L3
Ι
> OFF L3
Ι
p OFF L3
Ι
>>> OFF L3
O/C TRIP 1p.L3
or
O/C TRIP L123
7214 or
7215
Ι
>> OFF E
Ι
> OFF E
Ι
p OFFE
Ι
>>> OFF E
O/C TRIP L123
7215
Ι
>> OFF L1
Ι
>> OFF L2
Ι
>> OFF L3
Ι
>> OFF E
Figure 2-16
Figure 2-16
Figure 2-16
Figure 2-16
O/C TRIP I>>
7221
Ι
> OFF L1
Ι
> OFF L2
Ι
> OFF L3
Ι
> OFF E
O/C TRIP I>
7222
Ι
p OFF L1
Ι
p OFF L2
Ι
p OFF L3
Ι
p OFF E
Figure 2-17
Figure 2-17
Figure 2-17
Figure 2-17
O/C TRIP Ip
7223
Ι
>>> OFF L1
Ι
>>> OFF L2
Ι
>>> OFF L3
Ι
>>> OFF E
Figure 2-19
Figure 2-19
Figure 2-19
Figure 2-19
I-STUB TRIP
7235
(General TRIP)
O/C TRIP
7211
Setting Notes
General
During configuration of the scope of functions for the device (address 126) the available characteristics were
determined. Depending on the configuration and the order variant, only those parameters that apply to the
selected characteristics are accessible in the procedures described below.
At address 2601
Operating Mode
you switch time overcurrent protection
ON
- or
OFF
.
If not all stages are required, each individual stage can be deactivated by setting the pickup threshold to ∞.
But if you set only an associated time delay to ∞ this does not suppress the pickup signals but prevents the
timers from running.
One or several stages can be set as instantaneous tripping stages when switching onto a fault. This is chosen
during the setting of the individual stages (see below). To avoid a spurious pick-up due to transient overcur-
rents, the delay
SOTF Time DELAY
(address 2680) can be set. Typically, the presetting of 0s is correct. A
2.3.3
Functions
2.3 Overcurrent protection (optional)
SIPROTEC 4, 7VK61, Manual
75
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...