The order numbers of the exchange modules can be found in the Appendix in Section
Accessories.
RS232 Interface
Interface RS232 can be modified to interface RS485 and vice versa (see Figures
).
shows the C-CPU-2 PCB with the layout of the modules.
The following figure shows the location of the jumpers of interface RS232 on the interface module.
Surface-mounted devices with fiber optics connection have their fiber optics module fitted in the console
housing on the case bottom. The fiber optics module is controlled via an RS232 interface module at the associ-
ated CPU interface slot. For this application type the jumpers X12 and X13 on the RS232 module are plugged
in position 2-3.
[steckbruecken-rs232-020313-kn, 1, en_GB]
Figure 3-12
Location of the jumpers for configuration of RS232
Terminating resistors are not required for RS232. They are disconnected.
Jumper X11 is used to activate the flow control which is important for the modem communication.
Table 3-19
Jumper setting for CTS (Clear To Send, flow control) on the interface module.
Jumper
/CTS from Interface RS232
/CTS controlled by /RTS
X11
1-2
2-3
1)
1)
delivery condition
Jumper setting 2-3: The connection to the modem is usually established with a star coupler or fiber-optic
converter. Therefore the modem control signals according to RS232 standard DIN 66020 are not available.
Modem signals are not required since the connection to the SIPROTEC 4 devices is always operated in the half-
duplex mode. Please use the connection cable with order number 7XV5100-4.
Jumper setting 1-2: This setting makes the modem signals available, i. e. for a direct RS232-connection
between the SIPROTEC 4 device and the modem this setting can be selected optionally. We recommend to use
a standard RS232 modem connection cable (converter 9-pin to 25-pin).
i
i
NOTE
For a direct connection to DIGSI with interface RS232 jumper X11 must be plugged in position 2-3.
RS485 Interface
The following figure shows the location of the jumpers of interface RS485 on the interface module.
Interface RS485 can be modified to
interface RS232 and vice versa.
Mounting and Commissioning
3.1 Mounting and Connections
SIPROTEC 4, 7VK61, Manual
197
C53000-G1176-C159-5, Edition 05.2018
Summary of Contents for SIPROTEC 4 7VK61
Page 8: ...8 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 10: ...10 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 16: ...16 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 176: ...176 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 224: ...224 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 264: ...264 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 270: ...270 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 276: ...276 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...
Page 346: ...346 SIPROTEC 4 7VK61 Manual C53000 G1176 C159 5 Edition 05 2018 ...