Figure 2-25
Logic diagram of the overvoltage protection for phase voltage
Phase-to-phase overvoltage
The phase-to-phase overvoltage protection operates just like the phase-to-earth protection except that it
detects phase-to-phase voltages. Accordingly, phase-to-phase voltages which have exceeded one of the stage
thresholds
Uph-ph>
(address 3712) or
Uph-ph>>
(address3714 are also indicated. Beyond this, applies in
The phase-to-phase overvoltage protection can also be blocked via a binary input
>Uph-ph>(>) BLK
.
Functions
2.5 Under and over-voltage protection (optional)
98
SIPROTEC 4, 7VK61, Manual
C53000-G1176-C159-5, Edition 05.2018