[stoerfallverlauf-mit-stromkriterium-260602-kn, 1, en_US]
Figure 2-50
Typical fault profile for load side connection of the voltage transformers (with current supervi-
sion)
Upon the closing of the circuit breaker, current criterion is delayed for a short period of time. If the voltage
criterion drops out during this time period (about 60 ms), the protection function does not pick up. Therefore
no fault record is created when voltage protection is activated in a healthy system. It is important to under-
stand, however, that if a low voltage condition exists on the load after the circuit breaker is closed (unlike
), the desired pickup of the element will be delayed by 60 ms.
The following figure shows the logic diagram of the undervoltage protection function.
Functions
2.6 Voltage Protection 27, 59
SIPROTEC 4, 7SJ62/64, Manual
131
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...