[lo-recl-rel-qvp-20120319, 2, en_US]
Figure 2-67
Logic diagram of QU protection restarting
Setting Notes
General
Configuration of the protection functions at address 155
27/Q-Protection
defines whether the QU protec-
tion is
Enabled
or
Disabled
.
At address 5501
27/Q-Protection
the QU protection function can be switched
ON
or
OFF
.
The release current is entered at address 5502
I-Release
. The default setting is at 10 % of the rated current.
The threshold is one of the pickup criteria for tripping.
At address 5503
Inrush blk
you can activate the blocking when inrush has been detected.