[7sj62-64-iefger-aktiv-20120611, 1, en_US]
Figure 2-100
Activation of the directional intermittent ground fault protection
Measurand Acquisition
The intermittent ground fault current 3I0 is measured exclusively via the sensitive ground current input INs
(4th current transformer input) of the device.
Also the displacement voltage V
0
or 3 · V
0
is required to determine the direction. The displacement voltage V
0
can be applied directly to the device, or the summation voltage 3 · V
0
can be calculated from the three phase-
to-ground voltages.
If the displacement voltage is calculated, then:
3 · V
0
= V
A
+ V
B
+ V
C
If the displacement voltage is directly applied to the device, then V
0
is the voltage at the device terminals. It is
not affected by parameter
Vph / Vdelta
(address 206).
Fault Log, Ground Fault Log, Fault Recording
Parameter
Dir. Interm. EF
allows you to define the type of fault handling and fault logging. If set to ON,
tripping is possible and a fault log is generated. If set to
ON
with
ON with GF log
, tripping is possible, a
fault log and a ground fault log are generated. If set to
Alarm Only
, no tripping is possible. Only an alarm is
generated. Furthermore, only a ground fault log is created.
The raising pickup of the function (indication 6972
dIEF pick up
) is the criterion for opening the ground
fault log.
Logic Diagram
The following figure shows the logic diagram of the directional intermittent ground fault protection function.
Functions
2.15 Dir. Intermittent earth fault protection
232
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...