Synchronization Function
The synchronization function of 7SJ64 provides configuration options for four individual synchronization func-
tions. 7SJ62 only provides one function group for the synchronization check. The function and mode of opera-
tional according to SYNC Function group 1is described as follows. The same applies to function groups 2 to 4.
SYNC Function group 1
When connecting two sections of a power system, the synchrocheck verifies that the switching does not
endanger the stability of the power system.
Applications
•
Typical applications are, for example, the synchronism check of a feeder and a busbar (see Figure 2-122)
or the synchronism check of two busbars via bus coupler (see
Prerequisites
In 7SJ62 only one SYNC function group exists. Furthermore, only the operation mode
SYNCHROCHECK
is avail-
able for 7SJ62.
General
For comparing the two voltages the synchronism check uses the reference voltage V
1
and an additional
voltage to be connected V
2
.
If a transformer is connected between the two voltage transformers (
), its vector group can be
adapted in the 7SJ62/64 relay so that there are no external adjustment required.
[synchronisierfunktion-einspeisung-260602-kn, 1, en_US]
Figure 2-124
Infeed
2.21
2.21.1
2.21.1.1
Functions
2.21 Synchronization Function
SIPROTEC 4, 7SJ62/64, Manual
289
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...