Parameters 6x44
dα SYNC α2> α1
and 6x45
dα SYNC α2< α1
confine the operating range for synchro-
nous switching. These two parameters allow an asymmetrical switching range to be configured (see
).
Moreover, the release time delay
T SYNC-DELAY
(address 6x46) can be set during which all synchronous
conditions must at least be fulfilled for the closing command to be generated after expiration of this time.
[zuschaltenbeisynchronennetzbedingungen-150502-kn, 1, en_US]
Figure 2-132
Switching under synchronous system conditions
[synchronisierfunktion-arbeitsbereichfuerspgund-freq-150502-kn, 1, en_US]
Figure 2-133
Operating range under synchronous and asynchronous conditions for voltage (V) and
frequency (f)
Synchrocheck
Address 6x50
dV SYNCHK V2>V1
and 6x50
dV SYNCHK V2>V1
can be used to configure the permitted
voltage difference also asymmetrically. The availability of two parameters enables an asymmetrical release
range to be set.
Parameters 6x52
df SYNCHK f2>f1
and 6x53
df SYNCHK f2<f1
determine the permissible frequency
differences. The availability of two parameters enables an asymmetrical release to be set.
Functions
2.21 Synchronization Function
302
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...