Addr.
Parameter
Setting Options
Default Setting
Comments
9022A
RTD 2 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 2: Location
9023
RTD 2 STAGE 1
-50 .. 250 °C; ∞
100 °C
RTD 2: Temperature Stage 1
Pickup
9024
RTD 2 STAGE 1
-58 .. 482 °F; ∞
212 °F
RTD 2: Temperature Stage 1
Pickup
9025
RTD 2 STAGE 2
-50 .. 250 °C; ∞
120 °C
RTD 2: Temperature Stage 2
Pickup
9026
RTD 2 STAGE 2
-58 .. 482 °F; ∞
248 °F
RTD 2: Temperature Stage 2
Pickup
9031A
RTD 3 TYPE
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected
RTD 3: Type
9032A
RTD 3 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 3: Location
9033
RTD 3 STAGE 1
-50 .. 250 °C; ∞
100 °C
RTD 3: Temperature Stage 1
Pickup
9034
RTD 3 STAGE 1
-58 .. 482 °F; ∞
212 °F
RTD 3: Temperature Stage 1
Pickup
9035
RTD 3 STAGE 2
-50 .. 250 °C; ∞
120 °C
RTD 3: Temperature Stage 2
Pickup
9036
RTD 3 STAGE 2
-58 .. 482 °F; ∞
248 °F
RTD 3: Temperature Stage 2
Pickup
9041A
RTD 4 TYPE
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected
RTD 4: Type
9042A
RTD 4 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 4: Location
9043
RTD 4 STAGE 1
-50 .. 250 °C; ∞
100 °C
RTD 4: Temperature Stage 1
Pickup
9044
RTD 4 STAGE 1
-58 .. 482 °F; ∞
212 °F
RTD 4: Temperature Stage 1
Pickup
9045
RTD 4 STAGE 2
-50 .. 250 °C; ∞
120 °C
RTD 4: Temperature Stage 2
Pickup
9046
RTD 4 STAGE 2
-58 .. 482 °F; ∞
248 °F
RTD 4: Temperature Stage 2
Pickup
Functions
2.22 Temperature Detection via RTD Boxes
SIPROTEC 4, 7SJ62/64, Manual
309
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...