Addr.
Parameter
Setting Options
Default Setting
Comments
9051A
RTD 5 TYPE
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected
RTD 5: Type
9052A
RTD 5 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 5: Location
9053
RTD 5 STAGE 1
-50 .. 250 °C; ∞
100 °C
RTD 5: Temperature Stage 1
Pickup
9054
RTD 5 STAGE 1
-58 .. 482 °F; ∞
212 °F
RTD 5: Temperature Stage 1
Pickup
9055
RTD 5 STAGE 2
-50 .. 250 °C; ∞
120 °C
RTD 5: Temperature Stage 2
Pickup
9056
RTD 5 STAGE 2
-58 .. 482 °F; ∞
248 °F
RTD 5: Temperature Stage 2
Pickup
9061A
RTD 6 TYPE
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected
RTD 6: Type
9062A
RTD 6 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 6: Location
9063
RTD 6 STAGE 1
-50 .. 250 °C; ∞
100 °C
RTD 6: Temperature Stage 1
Pickup
9064
RTD 6 STAGE 1
-58 .. 482 °F; ∞
212 °F
RTD 6: Temperature Stage 1
Pickup
9065
RTD 6 STAGE 2
-50 .. 250 °C; ∞
120 °C
RTD 6: Temperature Stage 2
Pickup
9066
RTD 6 STAGE 2
-58 .. 482 °F; ∞
248 °F
RTD 6: Temperature Stage 2
Pickup
9071A
RTD 7 TYPE
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected
RTD 7: Type
9072A
RTD 7 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 7: Location
9073
RTD 7 STAGE 1
-50 .. 250 °C; ∞
100 °C
RTD 7: Temperature Stage 1
Pickup
9074
RTD 7 STAGE 1
-58 .. 482 °F; ∞
212 °F
RTD 7: Temperature Stage 1
Pickup
9075
RTD 7 STAGE 2
-50 .. 250 °C; ∞
120 °C
RTD 7: Temperature Stage 2
Pickup
Functions
2.22 Temperature Detection via RTD Boxes
310
SIPROTEC 4, 7SJ62/64, Manual
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...