Addr.
Parameter
Setting Options
Default Setting
Comments
9076
RTD 7 STAGE 2
-58 .. 482 °F; ∞
248 °F
RTD 7: Temperature Stage 2
Pickup
9081A
RTD 8 TYPE
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected
RTD 8: Type
9082A
RTD 8 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 8: Location
9083
RTD 8 STAGE 1
-50 .. 250 °C; ∞
100 °C
RTD 8: Temperature Stage 1
Pickup
9084
RTD 8 STAGE 1
-58 .. 482 °F; ∞
212 °F
RTD 8: Temperature Stage 1
Pickup
9085
RTD 8 STAGE 2
-50 .. 250 °C; ∞
120 °C
RTD 8: Temperature Stage 2
Pickup
9086
RTD 8 STAGE 2
-58 .. 482 °F; ∞
248 °F
RTD 8: Temperature Stage 2
Pickup
9091A
RTD 9 TYPE
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected
RTD 9: Type
9092A
RTD 9 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD 9: Location
9093
RTD 9 STAGE 1
-50 .. 250 °C; ∞
100 °C
RTD 9: Temperature Stage 1
Pickup
9094
RTD 9 STAGE 1
-58 .. 482 °F; ∞
212 °F
RTD 9: Temperature Stage 1
Pickup
9095
RTD 9 STAGE 2
-50 .. 250 °C; ∞
120 °C
RTD 9: Temperature Stage 2
Pickup
9096
RTD 9 STAGE 2
-58 .. 482 °F; ∞
248 °F
RTD 9: Temperature Stage 2
Pickup
9101A
RTD10 TYPE
Not connected
Pt 100 Ω
Ni 120 Ω
Ni 100 Ω
Not connected
RTD10: Type
9102A
RTD10 LOCATION
Oil
Ambient
Winding
Bearing
Other
Other
RTD10: Location
9103
RTD10 STAGE 1
-50 .. 250 °C; ∞
100 °C
RTD10: Temperature Stage 1
Pickup
9104
RTD10 STAGE 1
-58 .. 482 °F; ∞
212 °F
RTD10: Temperature Stage 1
Pickup
Functions
2.22 Temperature Detection via RTD Boxes
SIPROTEC 4, 7SJ62/64, Manual
311
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...