[schema-lsw-171103-kn, 1, en_US]
Figure 2-138
Diagram of CB maintenance procedures
The Σ
Ι
procedure is always present and active as a basic functionality. However, the other procedures (Σ
Ι
x, 2P
and
Ι
2
t) can be selected via a common configuration parameter.
As the load on the switch depends on the current amplitude and duration of the actual switching action,
including arc deletion, determination of the start and end criteria is of great importance. The procedures Σ
Ι
x,
2P and
Ι
2
t make use of the same criteria for that purpose. The logic of the start and end criterion is illustrated
in
.
The start criterion is fulfilled by an internal protective tripping initiated by the group indication "device TRIP".
Trips initiated via the internal control function are taken into consideration for the circuit breaker maintenance
if the respective command is indicated via the parameter 265
Cmd.via control
. An externally initiated trip
command can be taken into consideration if the message
>52 Wear start
is sent simultaneously via a
binary input. The edge of the sent message
>52-a
can also be used as a further criterion as this signals that
the mechanism of the circuit breaker is put in motion in order to separate the contacts.
As soon as the start criterion has been fulfilled, the parameterized opening time of the circuit breaker is
started. The time of commencement of separation of the circuit breaker contacts is thus determined. The end
of the trip procedure, including arc deletion is determined via another given parameter (CB tripping time)
supplied by the manufacturer of the circuit breaker.
In order to prevent an incorrect calculation procedure in case of circuit breaker failure, the current criterion
212
BkrClosed I MIN
verifies whether the current actually returned to zero after two additional cycles.
When the phase-selective logic release is fulfilled by the current criterion, the calculation and evaluation
methods of the respective procedures are initiated. After these have been completed, the end criterion of the
circuit breaker maintenance is fulfilled and ready for a new initiation.
Please note that CB maintenance will be blocked if parameter settings are made incorrectly. This condition is
indicated by the message
52 WearSet.fail
,
52WL.blk n PErr
or
52WL.blk I PErr
(see Section
, “Power System Data 2”). The latter two indications can only take effect if the 2P-proce-
dure was configured.
Functions
2.25 Auxiliary Functions
SIPROTEC 4, 7SJ62/64, Manual
321
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...