No.
Information
Type of
Informa-
tion
Comments
830
INs =
MV
INs Senstive Ground Fault Current
831
3Io =
MV
3Io (zero sequence)
832
Vo =
MV
Vo (zero sequence)
901
PF =
MV
Power Factor
991
Press =
MVU
Pressure
992
Temp =
MVU
Temperature
996
Td1=
MV
Transducer 1
997
Td2=
MV
Transducer 2
1068
Θ RTD 1 =
MV
Temperature of RTD 1
1069
Θ RTD 2 =
MV
Temperature of RTD 2
1070
Θ RTD 3 =
MV
Temperature of RTD 3
1071
Θ RTD 4 =
MV
Temperature of RTD 4
1072
Θ RTD 5 =
MV
Temperature of RTD 5
1073
Θ RTD 6 =
MV
Temperature of RTD 6
1074
Θ RTD 7 =
MV
Temperature of RTD 7
1075
Θ RTD 8 =
MV
Temperature of RTD 8
1076
Θ RTD 9 =
MV
Temperature of RTD 9
1077
Θ RTD10 =
MV
Temperature of RTD10
1078
Θ RTD11 =
MV
Temperature of RTD11
1079
Θ RTD12 =
MV
Temperature of RTD12
16031
φ(3Vo,INs) =
MV
Angle between 3Vo and INsens.
16032
In2 =
MV
In2
30701
Pa =
MV
Pa (active power, phase A)
30702
Pb =
MV
Pb (active power, phase B)
30703
Pc =
MV
Pc (active power, phase C)
30704
Qa =
MV
Qa (reactive power, phase A)
30705
Qb =
MV
Qb (reactive power, phase B)
30706
Qc =
MV
Qc (reactive power, phase C)
30707
PFa =
MV
Power Factor, phase A
30708
PFb =
MV
Power Factor, phase B
30709
PFc =
MV
Power Factor, phase C
30800
VX =
MV
Voltage VX
Average Measurements
The long-term averages are calculated and output by the 7SJ62/64.
Description
Long-Term Averages
The long-term averages of the three phase currents
Ι
x
, the positive sequence components
Ι
1
for the three
phase currents, and the real power P, reactive power Q, and apparent power S are calculated within a set
period of time and indicated in primary values.
For the long-term averages mentioned above, the length of the time window for averaging and the frequency
with which it is updated can be set.
2.25.4
2.25.4.1
Functions
2.25 Auxiliary Functions
SIPROTEC 4, 7SJ62/64, Manual
333
C53000-G1140-C207-8, Edition 08.2016
Summary of Contents for SIPROTEC 4
Page 8: ...8 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 18: ...18 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 30: ...30 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 540: ...540 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 594: ...594 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...
Page 720: ...720 SIPROTEC 4 7SJ62 64 Manual C53000 G1140 C207 8 Edition 08 2016 ...